Flair 310, Flair 370 2008
Transkrypt
Flair 310, Flair 370 2008
MV network management - Easergy range Technical data sheet 2008 Flair 310, Flair 370 Directional fault passage indicators for underground networks PE41001 Application The Flair 3xx directional fault passage indicators are designed for underground MV networks with isolated or compensated earthing. They can also be used on underground MV networks with impedant earthing. They provide a light indication allowing to localize the fault. Flair 370: 220 Vac + lithium battery power supply. Flair 310: lithium battery power supply (when no LV power supply available). Description Flair 3xx fault passage indicators are made of ABS polycarbonat sealable box. b Operation mode and functions: v adaptation to the voltage sensors using dip-switches, v various user configurable parameters: detection parameters, reset functions and output contact behaviour, v optional settings, test and reset functions by magnetic button. b Light indication Green, Red or alternate Green/Red blinking according to fault type and location. b Fault counters Number of transient and permanent faults. b Display: 4x12.7 mm digits Displays fault counters and optional settings. b 2 output contacts Indication of transient and/or permanent faults. b Directional detection of phase-to-earth faults Sensors b Default settings fitting most applications PE55552 b Fully user configurable PE55553 b 2 types of current sensors installation are possible: v single CT installation: phase-to-earth faults only (installation on 3-core cable), v 3 phase CTs installation: phase-to-earth and phase-to-phase faults. b Detection of phase-to-phase faults b Lithium battery power supply MFD standard phase CT MFH 2200 earth fault CT TCR resin phase CT b Voltage sensors are capacitive dividers situated: v on MV/LV substations switchgears or transformers separable elbow connectors, v on air insulated substations busbars. Standard PE55557 PE55556 PE55555 Light indicators Flush mounted (wall < 6 mm) Anti-vandalism DE55561 Flair 3xx detection principle is based on the analysis of transients of residual voltage Vr (= 3 V0) and residual current Ir (= 3 I0), in the next ms following the fault. b At the time when the phase-to-earth fault occurs, the fault direction is determined according to phase comparison of Vr and Ir. kV A 10 100 0 0 Ir Vr -100 -10 b The fault will be confirmed if Vr is still present after a configurable time delay (default 50 ms). Indication of transient fault (counter and optionally output contact) will follow. b The fault will be confirmed as permanent (protection tripping or power presence under earth fault conditions) after the possible reclosing cycles before starting permanent fault indication (light indication and optionally output contact). This detection algorithm allows detecting earth faults up to approximately 200 Ω. Light indication DE55562 b Phase-to-earth fault MV feeder Green or off b Phase-to-phase or double phase-to-earth fault MV feeder Characteristics Application Network (standard: others, on request) (kV) Frequency (Hz) Neutral Phase-to-earth fault detection Residual current detection threshold (A peak) Residual voltage detection threshold (kV peak) Residual voltage required for fault confirmation (kV r ms) Residual voltage r ms minimum duration (ms) Minimum total capacitive current required (A) Minimum capacitive current for indication downstream fault (A) Light indication Double phase-to-earth fault detection Tripping threshold (A) 10 to 25 (according to voltage sensor) 50 Compensated - isolated - impedant 40 0.3 x Un (e.g.: 6 kV peak for Un = 20 kV) 0.18 x Un (e.g.: 3.5 kV r ms for Un = 20 kV) 50* to 500 50 30 Red: earth fault towards cable Green: earth fault towards busbar 100, 120, 140, 160*, 180, 200, 220, 240, 260, 280, 300 50, 60, 70*, 80, 90, 100, 120,140, 160, 180, 200, 250, 300, 350, 400, 450, 500 Alternate Red/Green Time delay (ms) Light indication Phase-to-phase fault detection Tripping threshold (A) Time delay (ms) Light indication Time delays Before indication of transient fault (counter and output contact) (s) Before indication of permanent faults (light indication and output contact) (s) Duration of MV required for any fault detection (inrush restraint) (s) Reset of fault indication By restoration of MV without fault for a duration of (s) After configurable time delay (h) Manual Light indication Flashing period (s) Dry output contact Breaking capacity Environment Vibration withstand (IEC 68-2-6 & 68-2-29) (g) Operating temperature (°C) Storage temperature (°C) Protection grade Mechanical characteristics Dimension H x L x P (mm) Weight (kg) 200, 250, 300, 350, 400, 450, 500* 50, 60, 70*, 80, 90, 100, 120,140, 160, 180, 200, 250, 300, 350, 400, 450, 500 Alternate Red/Green 1.1 Off-10-40-70*-120-240 5 5 (note: can be disabled) 2, 4*, 6, 8, 12, 16 With a magnet 1 8 A/250 Vac; 5 A/30 Vdc 2 – 25 to + 55 – 25 to + 70 IP 21 IK 9 270 x 203 x 110 1.5 (*) Default value. Device Power supply Lithium battery Reference 220 Vca (± 10%), + lithium battery (10 kV isolated) Battery life duration Flair 310 Flair 370 b CTs MFD TCR MFH 2200 IC 30C Internal Ø (mm) External Ø (mm) 70 160 55 120 130 200 3 m cable for MFH 2200 59990** C2991753** 59927 59998 Light indicators BVE-D LED-D BVD Type Standard Flush-mounted into wall < 6 mm Anti-vandalism 59988 59989 59961 b > 7 years* > 10 years* 59979 59980 ART.95988 © Schneider Electric Industries SAS - All rights reserved Detection principle (*) Including 200 hours blinking. (**) Kit of 3 CTs with connection bundle. Consult us for voltage sensors, if necessary. Schneider Electric Industries SAS 89, boulevard Franklin Roosevelt F-92505 Rueil-Malmaison Cedex Tél. : +33 (0)1 41 29 85 00 www.schneider-electric.com www.easergy.com AMTED304009EN As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Publishing: Schneider Electric Production: Schneider Electric Printing: Imprimerie du Pont de Claix This document has been printed on ecological paper 08-2008