Important Service Bulletin:
e-Brick Earthing
SERVICE BULLETIN 1003 Issue 1 - Page 1 of 2
1. e-Brick Earthing – Systems with GEW Power Distribution Units.
All new UV systems will now be supplied with a supplementary earth cable on each power
distribution unit (PDU). The cable(s) must be connected directly (not ‘daisy chained’) to
the main earth bar on the printing press. Its purpose is to common-earth circuits together.
Each PDU will still require a direct mains earth connection.
Supplementary earth cable(s) must be connected to press main earth bar.
Each e-Brick must also have the
auxiliary earth connection made to the
earth connection block.
e-Brick auxiliary earth connection.
Earth connection block.
2. e-Brick Earthing – Systems without GEW Power Distribution Units.
For those systems that do not have a GEW supplied power distribution unit an individual
earth cable is supplied and fitted to each e-Brick. These earth cables should be
connected directly (not ‘daisy chained’) to the printing press main earth bar.
Connect to printing press main earth bar.
Note: To maintain good earth continuity it is important to make sure that each
printing press frame is adequately earthed to a common earth bar. A schematic
diagram is shown overleaf. Keep all earth cables as short as possible.
UK Office: GEW (EC) Limited
Tel: +44 (0)1737 824500
Fax: +44 (0)1737 823822
GEW Vertriebsbüro Deutschland
Tel: +49 (0)7022 3039769
Fax: +49 (0)7022 3039770
American Office: GEW, Inc.
Tel: +1 440 237 4GEW (4439)
Fax: +1 440 230 4GEW (4439)
Indian Office: GEW Asia Pvt. Ltd.
Tel: +91 22 2528 5442
Fax: +91 22 2528 5443
●- [email protected] -●- www.gewuv.com -●- [email protected] -●- www.gewuv.com -●- [email protected] -●
PSU2
PSU3
PSU5
EARTH
CONNECTIONS
TO PRESS
(MIN 16MM²)
PSU4
EARTH TO UV
DISTRIBUTION (MIN 35MM²)
PSU7
UV LAMPHEAD
PSU6
PRINT STATION
PSU8
PROJECT TITLE:
OPTIONAL EARTH SPIKE RECOMMENDED WHEN DISTANCE TO MAIN DISTRIBUTION
IS GREATER THAN 100M, AND IN AREAS PRONE TO LIGHTENING STRIKES.
ENSURE THAT ALL SECTIONS OF THE PRESS ARE SUITABLY EARTHED.
NOTES:
YELLOW - CABLES WITH EARTH INCLUDED.
GREEN - ADDITIONAL SUPPLEMENTARY EARTHING.
EARTH LINK LAMPHEAD TO
PRINT STATION
(MIN 6MM²)
EARTH BAR
MIN. 20x3MM
OPTIONAL
EARTH
SPIKE
PSU1
SECONDARY EARTHS
FROM EACH PSU TO
UV DISTRIBUTION
(MIN 6MM²)
UV LAMPHEAD
DRAWING TITLE:
PRESS
PRESS DISTRIBUTION
AND ELECTRONICS
UV LAMPHEAD
PRINT STATION
UV LAMPHEAD
UV DISTRIBUTION
PRINT STATION
TO BUILDING MAINS DISTRIBUTION
PRINT STATION
TO BUILDING MAINS DISTRIBUTION
PRINT STATION
PROJECT NO
SHT
UV LAMPHEAD
UV LAMPHEAD
UV LAMPHEAD
PRINT STATION
UV LAMPHEAD
PRINT STATION
PRINT STATION
THIS DRAWING MUST
NOT BE REPRODUCED
OR DISTRIBUTED
WITHOUT THE
WRITTEN PERMISSION
OF GEW (EC) LIMITED.
WWW.GEWUV.COM
(0)1737 824 500
....engineering UV
GEW
DRAWING NUMBER
OPTIONAL
EARTH
SPIKE
EARTH TO PRESS
DISTRIBUTION (MIN 50MM²)