sinline - EVER Sp. z o.o.

Transkrypt

sinline - EVER Sp. z o.o.
PRODUCT CHARACTERISTICS
SINLINE
800, 1200, 1600, 2000, 3000
The next generation SINLINE-series battery back-ups
enable full protection of power supply to advanced
single- and multi CPU servers, PCs, computer termi
nals and small and medium networks.
- CBC – Cool Battery Charging – quick and efficient
charging system that cuts charging time and extends
the operating life of the back-up's accumulators
SAFEGUARDS
FEATURES
- Communication interface RS232
- AVR – automatic mains voltage regulation system
- Telecommunication filter
- PowerSoft Personal – monitoring software ensuring
complete control over computer workstations
- Technical support – 48h door-to-door service
The SINLINE series is equipped with unique systems
developed by EVER engineers:
- CDS – Clear Digital Sinus – system that enables the
battery back-up to generate true sine wave output
voltage in battery operation mode
www.ever.eu
- Against overloads
- Against shorting
- Against overvoltage
- Against incorrect connection
SINLINE
MODEL
800, 1200, 1600, 2000, 3000
SINLINE 800
Output power (apparent/active) 1)
800VA/520W
Technology
Case type
MAINS OPERATION MODE
Input voltage 2)
Frequency of input voltage
Range of output voltage 2)
Shape of output voltage
Switching thresholds: mains - UPS 2)
Time to switch to UPS
Filtering of output voltage
BACK-UP (BATTERY) OPERATION MODE
Output voltage
Frequency of output voltage
Shape of output voltage
Switching thresholds: UPS – mains 2)
Switching time: UPS – mains
Filtering of output voltage
Shorting safeguard
Overload protection
UPS
(100%/80%/50% Pmax) UPS + battery module
Support time
Warning! The manufacturer reserves the right to change the abovementioned parameters without notice.
Accumulator
capacity
UPS charging time 3)
UPS
5/7/12 min
2 x 12V 5Ah
Battery module
UPS
5h
UPS + battery module
SINLINE 1200
SINLINE 1600
SINLINE 2000
SINLINE 3000
1200VA/780W 1600VA/1040W 2000VA/1300W 3000VA/1950W
line-interactive (VI)
Tower
~160 - 264V (~145 - 280V) ± 2%
45 - 55Hz ± 1Hz
~184 - 264V (~167 - 280V) ± 2%
same as input but filtered
~160V / 264V (~145V / 280V) ± 2%
<3 ms
noise filter RFI-EMI varistor damper
~230V ± 5%
50Hz ± 1Hz
sinus
~165V / ~259V (~150V / ~275V) ± 2%
0 ms
LC
Electronic
Electronic
4/5/8 min
4/5/9 min
4,5/6/10 min
2 x 12V 7Ah 3 x 12V 5Ah 4 x 12V 5Ah
7h
5h
5h
-
3/4/8 min
4 x 12V 7Ah
7h
MECHANICAL PARAMETERS
Dimensions in [mm] UPS
(h x w x d)
Battery module
Weight
UPS
Battery module
ENVIRONMENTAL PARAMETERS
Working environment
Operating / storage temperature 4)
Relative humidity for operation /
storage
Altitude above sea level 5)
EQUIPMENT
Number and type of outlet sockets
Signalling
Overcurrent protection
Telephone line / LAN filter
Communication interface
Software
14kg
190 x 165 x 480
16kg
20kg
-
190x165x640
23kg
28kg
Rooms with low level of pollution
+10oC - +35oC / 0oC - +45oC
20 - 80% / 20 - 95% (without condensation)
up to 1000m
4 x PL
sound and LED
fuse
circuit breaker
+/RS 232
PowerSoft Personal
1) For normal operation of the battery back-up the load connected to its output should not exceed 80% of value indicated in the table. Reserve power is essential to ensure continuous operation of
connected devices in case of momentary rushes in load current.
2) User may modify the switching thresholds within the range provided. Default setting is provided in parentheses.
3) After discharging the UPS with 0.8 Pmax power – charging the battery to 90% capacity.
4) Continued exposure of the battery back-up to the ambient temperature exceeding +25°C will shorten the life of batteries.
5) If the altitude above sea level increases beyond the provided limit the permitted load power of the batter back-up decreases.
SINLINE
800, 1200, 1600, 2000, 3000
FRONT PANEL
1) A column of green LEDs indicating the charge level of
the accumulator.
2) Power switch
3) LED indicating whether the AVR (Automatic Voltage
Regulation) system is engaged
4) Two-colour LED indicating the operating mode:
a. mains operation mode
b. battery operation mode
5) A column of LEDs (three green, top one red) indicating
the load of the battery back-up in percents.
REAR PANEL
6) Outlet sockets
7) Port for communication with a PC via RS232
8) Telecommunication filter sockets RJ 11
9) Power cord
10) Cut-out (fuse in back-ups with power of 800VA, 1200VA
and 1600VA; circuit breaker in back-ups with power of
2000VA and 3000VA)
EVER Sp. z o.o. ul. Grudziñskiego 30, 62-020 Swarzêdz
tel. 0048 61 6500 400, fax 0048 61 6510 927, e-mail: [email protected]