CZĘŚĆ OGÓLNA................................................................................................................................................. 3 1.1. Przedmiot opracowania ............................................................................................................................. 3 1.2 Podstawa opracowania .......................................................................................................................... 3 1.3 Cel opracowania .................................................................................................................................... 3 1.4 Inwestor ................................................................................................................................................. 3 1.6 Zakres opracowania ............................................................................................................................... 3 1.7 Opracowania związane .......................................................................................................................... 4 1.8 Wykaz zastosowanych norm i przepisów Normy:................................................................................. 4 1.9. Uzgodnienia ............................................................................................................................................... 5 CZĘŚĆ TECHNICZNA ....................................................................................................................................... 6 2. System DSO opis ogólny. .................................................................................................................................. 6 2.1 Opis obiektu........................................................................................................................................... 6 2.2 Strefy ewakuacyjne................................................................................................................................ 6 2.3 Projekt Akustyczny.............................................................................................................................. 11 2.4 Projekt elektroakustyczny. ....................................................................................................................... 12 2.5 Pamięć komunikatów. ......................................................................................................................... 12 2.6 System zasilania dedykowanego. ........................................................................................................ 12 2.7 Współpraca z centralą CSP. ................................................................................................................. 13 2.8 Okablowanie. ....................................................................................................................................... 13 2.9 Głośniki. .............................................................................................................................................. 14 2.9.1. Głośniki typy i modele. ....................................................................................................................... 14 2.9.2. Charakterystyka głośników. ................................................................................................................ 14 2.9.3. Parametry akustyczne.......................................................................................................................... 17 2.9.4. Zastrzeżenie projektowe. ..................................................................................................................... 17 2.9.4. Lokalizacja szczegółowa głośników. .................................................................................................. 17 2.10. Dobór linii głośnikowych. ...................................................................................................................... 21 2.11. Moduły kontroli linii. ............................................................................................................................. 22 2.12. Dobór wzmacniaczy mocy. .................................................................................................................... 22 2.13. Pomieszczenie centrali DSO. ................................................................................................................. 22 2.14. Drabinka priorytetów. .......................................................................................................................... 22 2.15. Dokumenty związane z DSO. ................................................................................................................. 22 2.15.1. Dokumentacja powykonawcza .......................................................................................................... 23 2.15.2. Instrukcja obsługi .............................................................................................................................. 23 2.15.3. Dziennik pracy systemu .................................................................................................................... 23 2.15.4. Instrukcje konserwacji....................................................................................................................... 23 3. Warunki techniczne instalacji ........................................................................................................................ 24 3.1. Instalacja systemu. ..................................................................................................................................... 24 3.2. Zalecenia instalacyjne: ............................................................................................................................... 25 3.3. Zalecenia eksploatacyjne. .......................................................................................................................... 25 3.4. Zalecenia dla Inwestora.............................................................................................................................. 25 3.5. Uwagi dla innych branż. ............................................................................................................................ 25 3.5.1. Instalacja elektryczna ...................................................................................................................... 26 3.5.2. Integracja systemów ........................................................................................................................ 26 3.6. Uwagi ogólne ............................................................................................................................................. 26 4. Zalecenia dla użytkownika instalacji............................................................................................................. 27 4.1 Zalecenia ogólne .................................................................................................................................. 27 4.2 Szkolenie personelu obsługi ................................................................................................................ 27 4.3 Konserwacja systemu DSO ......................................................................................................................... 27 5. Zestawienie materiałów .................................................................................................................................. 28 6. Przedmiary robót. ........................................................................................................................................... 30 8. Oświadczenia i uprawnienia projektanta i sprawdzającego. .................................................................. 34 7. Zestawienie rysunków..................................................................................................................................... 35 Rys. 1: Schemat blokowy Dźwiękowego Systemu Ostrzegawczego DSO. ...................................................... 35 Rys. 2: Instalacja systemu DSO– rzut łącznika hali – poziom -500.................................................................. 35 Rys. 3: Instalacja systemu DSO– rzut hali poziom +0,00. ................................................................................ 35 Rys. 4: Instalacja systemu DSO– rzut hali poziom +350. ................................................................................. 35 Rys. 5: Instalacja systemu DSO– rzut hali poziom +910. ................................................................................. 35 9. Certyfikaty i dane techniczne – karty urządzeń i elementów. ................................................................. 35 2
CZĘŚĆ OGÓLNA
1.1.
Przedmiot opracowania
Przedmiotem opracowania jest projekt techniczny wykonawczy Dźwiękowego
Systemu Ostrzegawczego (DSO) dla nowo projektowanej hali wystawienniczej w
obiekcie ARENA OSTRÓDA CENTRUM TARGOWO-KONFERENCYJNE WARMII I
MAZUR. Zainstalowany Dźwiękowy System Ostrzegawczy zapewni dodatkową
ochronę osób przebywających w obiekcie poprzez automatyczne powiadomienie ich
o wystąpieniu zagrożenia pożarowego oraz umożliwi bezpośrednie kierowanie
ewakuacją tych osób z zagrożonych stref i z całego obiektu za pomocą komunikatów
głosowych. Projektowany system będzie zintegrowany z systemem dla hal już
istniejących.
1.2
Podstawa opracowania
Podstawą opracowania jest:
ƒ Zlecenie Zamawiającego.
ƒ Wykonana instalacja systemu DSO Etap I.
ƒ Wykonana instalacja systemu SAP Etap I.
ƒ Projekt instalacji systemu SAP Etap II.
ƒ Dokumentacja architektoniczna – z inwentaryzacji.
ƒ Wymagania techniczno - budowlane w zakresie
przeciwpożarowego.
ƒ Dane katalogowe systemu DSO.
ƒ Obowiązujące normy i przepisy.
ƒ Projekt budowlany.
1.3
zabezpieczenia
Cel opracowania
Celem opracowania jest przedstawienie w formie dokumentacji technicznej
projektowej wykonawczej sposobu instalacji, uruchomienia i konfiguracji
dźwiękowego systemu ostrzegawczego na potrzeby nowo projektowanej hali
wystawienniczej w ARENA OSTRÓDA CENTRUM TARGOWO-KONFERENCYJNE
WARMII I MAZUR.
1.4 Inwestor
Inwestorem niniejszej inwestycji jest „DEMUTH ALFA SP. Z.O.O. OSTRÓDA”
SPÓŁKA KOMADYTOWO-AKCYJNA, UL. GRUNWALDZKA 211, 80-266
GDAŃSK.
1.6
Zakres opracowania
Niniejszy projekt obejmuje wykonanie dźwiękowego systemu ostrzegawczego w
oparciu o urządzenia firmy Amabient System typu Venas dla nowo projektowanej hali
wystawienniczej w ARENA OSTRÓDA CENTRUM TARGOWO-KONFERENCYJNE
WARMII I MAZUR.
Zaprojektowany system będzie włączony i zintegrowany z już istniejącym system
DSO dla Etapu I przedsięwzięcia.
W skład systemu wchodzą następujące urządzenia:
ƒ Menadżer systemu
ƒ Jednostka kontroli
3
Wzmacniacze mocy
Jednostka zarządzająca systemem zasilania
Mikrofon strażaka
Mikrofony strefowe w ilości dostosowanej do potrzeb użytkownika.
Zasilacze.
Głośniki panelowe ścienne i sufitowe oraz tubowe zewnętrzne,
Moduły odłączający lokalne nagłośnienia w poszczególnych teatrach oraz w
kawiarni.
Projekt zawiera opis projektowanych tras kablowych pętli zasilających głośniki, linii
sterujących i monitorujących oraz montaż wszelkich dodatkowych urządzeń
niezbędnych do prawidłowego funkcjonowania systemu DSO w oparciu o
dokumentację techniczną systemu i niezbędne uzgodnienia z inwestorem.
Wszelkie proponowane urządzenia posiadają certyfikaty zezwalające na ich
użytkowanie w ochronie przeciwpożarowej na terenie Rzeczpospolitej Polskiej
wydane przez Centrum Naukowo - Badawcze Ochrony Przeciwpożarowej w
Józefowie.
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
1.7
Opracowania związane
Operat pożarowy - „Wytyczne techniczne dla zapewnienia ochrony
przeciwpożarowej obiektu ARENA OSTRÓDA CENTRUM TARGOWOKONFERENCYJNE WARMII I MAZUR".
ƒ warunki techniczne i eksploatacyjne dla instalacji dźwiękowego systemu
ostrzegawczego;
ƒ „Analiza akustyczna. Symulacja akustyczna
Dźwiękowego Systemu
Ostrzegawczego dla hali wystawienniczej Etap II obiektu ARENA OSTRÓDA
CENTRUM TARGOWO-KONFERENCYJNE WARMII I MAZUR.”
ƒ dokumentacja techniczna budowlana - architektoniczna.
ƒ
1.8
Wykaz zastosowanych norm i przepisów Normy:
ƒ PN-EN 60849:2001 Dźwiękowy system ostrzegawczy.
ƒ PN-ISO 8421-6:1997 Ochrona przeciwpożarowa. Terminologia. Ewakuacja i
środki ewakuacji.
ƒ PN EN-54 1-20 Ochrona przeciwpożarowa budynków.
ƒ PN-E-08350-14 z 2002r. Ochrona przeciwpożarowa budynków. Konserwacja
systemów.
ƒ PN-76/E-05125 Elektroenergetyczne i sygnalizacyjne linie kablowe.
Projektowanie i budowa.
ƒ PN - IEC 60364-4-42:1999 Instalacje elektryczne w obiektach budowlanych.
Ochrona dla zapewnienia bezpieczeństwa. Ochrona przed skutkami
oddziaływania cieplnego.
ƒ PN -IEC 60364-4-482:1999 Instalacje elektryczne w obiektach budowlanych.
Ochrona dla zapewnienia bezpieczeństwa. Dobór środków ochrony w
zależności od wpływów zewnętrznych. Ochrona przeciwpożarowa.
ƒ PN-EN 54-1:1998 Systemy sygnalizacji pożarowej. Wprowadzenie.
ƒ PN - EC 60364-1 Instalacje elektryczne w obiektach budowlanych. Zakres,
przedmiot i wymagania podstawowe.
ƒ PN - IEC 60364-441 Instalacje elektryczne w obiektach budowlanych.
Ochrona dla zapewnienia bezpieczeństwa . Ochrona przeciwporażeniowa.
ƒ PN -IEC 60364-4-443 Instalacje elektryczne w obiektach budowlanych.
Ochrona dla zapewnienia bezpieczeństwa. Ochrona przed przepięciami
4
atmosferycznymi lub łączeniowymi
ƒ BN-84/8984-10
Zakładowe
sieci
telekomunikacyjne
przewodowe.
Instalacje wewnętrzne .Ogólne wymagania
ƒ BN-73/9371-03
Uziemienia urządzeń telekomunikacji przewodowej i
bezprzewodowej
Dokumenty:
1. Przepisy budowy urządzeń elektrycznych. PBUE, wyd. 1980 r.
2. Rozporządzenie Ministra budownictwa i Przemysłu Materiałów Budowlanych w
sprawie bezpieczeństwa i higieny pracy przy wykonywaniu robót budowlano
montażowych i rozbiórkowych. (Dz. U, Nr 13 z dn.10 .04 .1972 r).
3. Warunki techniczne wykonania i odbioru robót budowlano - montażowych - Część
V. Instalacje elektryczne, 1988 r.
4. Rozporządzenie Ministra Spraw Wewnętrznych i Administracji z dnia 21 kwietnia
2006 r. w sprawie ochrony przeciwpożarowej budynków, innych obiektów
budowlanych i terenów / Dz. U. z dnia 21 maja 2006r. nr 80, poz. 563 /.
5. Rozporządzenie Ministra Przemysłu z dnia 26.11.1990 r. w sprawie warunków
technicznych jakim powinny odpowiadać urządzenia elektroenergetyczne w
zakresie ochrony przeciwporażeniowej. (Dz. V. Nr 81 z dnia 26.11.1990 r.)
6. Instalacje elektryczne, COBO - PROFIL, Warszawa 1999 r.
7. Ustawa z dn. 24.08.1991 o ochronie przeciwpożarowej (Dz. U. z 2002r. Nr 147,
poz. 1229 i z 2003r. Nr 52, poz. 452)
8. Rozporządzenie Ministra Spraw Wewnętrznych i Administracji z dn. 16.06.2003r.
w sprawie uzgadniania projektu budowlanego pod względem ochrony
przeciwpożarowej (Dz. U. Nr 121, poz. 1137).
9. Rozporządzenie Ministra Infrastruktury z dnia 12.04.2002r. w sprawie warunków
technicznych jakim powinny odpowiadać budynki ( Dz. U. Nr 75, poz. 690)
10. Rozporządzenie Ministra Spraw Wewnętrznych i Administracji z dnia 22 kwietnia
1998 r. w sprawie wyrobów służących do ochrony przeciwpożarowej, które mogą
być wprowadzone do obrotu i stosowane wyłącznie na podstawie certyfikatu
zgodności.
11. Podręcznik projektanta systemów sygnalizacji pożarowej. Część I. Wymagania i
podstawy prawne, st. bryg. dr inż. Dariusz Ratajczak, Wstęp do automatycznych
systemów sygnalizacji pożarowej, mgr inż. Jerzy Ciszewski. Józefów k/Otwocka
16.10.2004r.
12. Podręcznik projektanta systemów sygnalizacji pożarowej. Część II. st. Kpt. mgr
inż. Janusz Sawicki, inż. Ryszard Strzemeski. Józefów k/Otwocka 16.10.2004r.
13. Instrukcje, materiały i wytyczne dostawcy urządzeń Venas.
1.9. Uzgodnienia
Dokumentację techniczną projektową budowlano-wykonawczą
rzeczoznawcą ds. zabezpieczeń pożarowych.
5
uzgodniono
z
CZĘŚĆ TECHNICZNA
2. System DSO opis ogólny.
2.1
Opis obiektu.
Hala wystawiennicza stanowi budynek o mieszanej strukturze – jednokondygnacyjna
hala wystawowa z pomieszczeniami użytkowymi, socjalnymi i technologicznymi
rozmieszczonymi na trzech kondygnacja z dwóch stron hali głównej. Projektowany
obiekt będzie połączony łącznikiem z istniejącymi obiektami MTM Ostróda
Obiekt zlokalizowany jest na skraju miasta z bezpośrednim dostępem kołowym z
zewnątrz oraz z placami parkingowymi - z jednej strony dostępnymi przez bramę.
Obiekt otoczony jest ogrodzeniami.
Instalacje funkcjonalne
Obiekt wyposażony jest w następujące instalacje:
• wodociągową
• hydrantową,
• kanalizacji sanitarnej,
• kanalizacji opadowej,
• centralnego ogrzewania wraz z kotłownią,
• ciepłej wody użytkowej,
• elektryczną i oświetlenia terenu,
• odgromową.
Według oświadczenia inwestora w budynku nie będą występowały materiały
niebezpieczne pożarowo.
2.2
Strefy ewakuacyjne.
Projektowany Dźwiękowy System Ostrzegawczy obejmie zasięgiem przestrzeń hali
wystawienniczej z pomieszczeniami użytkowymi, socjalnymi i technologicznymi
rozmieszczonymi na trzech kondygnacja z dwóch stron hali głównej oraz z
łącznikiem pomiędzy istniejącymi obiektami a nowo projektowanym. Zgodnie z
operatem przeciwpożarowym hala ta objęta jest trzema strefami pożarowymi.
Główna hala wystawiennicza została zaprojektowana jako cztery autonomiczne
obszary z możliwością ich separacji systemem ścian mobilnych. Hala ta składa się z
dwóch hal (A i B) a każda z nich może być podzielona na kolejne dwie hale (A1, A2,
B1, B2). Ten podział użytkowy ma wpływ na podział funkcjonalny systemu DSO,
który będzie również wykorzystywany do celów nagłośnieniowych i przywoławczych
niezależnie w poszczególnych strefach i obszarach obiektu.
Projektowany system DSO na całym obiekcie został podzielony na strefy
ewakuacyjne, umożliwiając w ten sposób kierowanie komunikatów do wybranych
przez operatora obszarów budynku. W omawianej hali ze względów konstrukcyjnych
i eksploatacyjnych dla systemu DSO ustanawia się jedną strefę ewakuacyjną, która
będzie zasilana w sygnały komunikatów z kilku linii głośnikowych zintegrowanych z
dla całego obiektu. Użytkownik może dowolnie skonfigurować pracę systemu
zgodnie z przyjętym scenariuszem postępowania w przypadku powstania alarmu
zagrożenia pożarowego.
6
Tabela 1. Zestawienie
wystawienniczej.
Strefa 1 2 3 Nr linii L1 L2 L3 4 L4 5 L5 6 L6 7 L7 8 L8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 L9 L10 L11 L12 L13 L14 L15 L16 L17 L18 L19 L20 L21 L22 L23 L24 stref
nagłośnieniowych
Obszar nagłaśniany Pomieszczenia obsługi Pomieszczenia obsługi Pomieszczenia techniczne Pomieszczenia ogólnodostępne Pomieszczenia techniczne Pomieszczenia ogólnodostępne Pomieszczenia techniczne Pomieszczenia ogólnodostępne Pomieszczenia techniczne Pomieszczenia techniczne Pomieszczenia techniczne Pomieszczenia ogólnodostępne Pomieszczenia techniczne Pomieszczenia techniczne Kawiarnia Łącznik Łącznik Hala A Część A1 (Lewa) Hala A Część A1 (Lewa) Hala A Część A2 (Prawa)) Hala A Część A2 (Prawa)) Pasaż Hala B Część B1 (Lewa) Hala B Część B1 (Lewa) Hala B Część B2 (Prawa)) Hala B Część B2 (Prawa)) Parkingi ‐ Elewacja południowa Parkingi ‐ Elewacja wschodnia Parkingi ‐ Elewacja wschodnia Parkingi ‐ Elewacja północna w
przestrzeni
hali
Poziomy obiektu ‐500 ‐500 ‐500 +0,00 +350 +0,00 +350 +0,00 +350 +910 +910 +0,00 +350 +910 ‐500 ‐500 ‐500 +0,00 +0,00 +0,00 +0,00 +0,00 +0,00 +0,00 +0,00 +0,00 +0,00 +0,00 +0,00 +0,00 Tabel 2. Zestawienie głośników w liniach głośnikowych oraz bilans mocy systemu DSO. 7
L1
Moc [W]
2 BILANS MOCY SYSTEMU DSO
Nr głośnika w linii
Liczba głośników
L.p.
Nr linii głośnikowej moc
pojedynczego głośnika
Tabel 1. Bilans mocy systemu DSO. 29
95,25
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
3 0,75W 1 1 1 1 4 1,5W 5 3W 1 1 6 6W 1 1 7 10W 8 15W 9 L2
1 1 1 1 1 1 1 1
1
1 7
5,25
2
3,00
1 1 11
33,00
1 9
54,00
0
0,00
0
0,00
1
1
1
1
1
1
1 1 31
100,50
6
4,50
1 2
3,00
15
45,00
8
48,00
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
10 0,75W 1 1 11 1,5W 12 3W 1 1 1 1 1 13 6W 1 1 14 10W 15 15W 16 L3
1 1 1 1 1 1 1
1
1 1 1
1
1 1 1 1 1 1 1 1 1
0
0,00
0
0,00
21
114,00
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
17 0,75W 0
0,00
18 1,5W 0
0,00
19 3W 1 1 4
12,00
20 6W 1 1 1 1 1 1 1 1 1 1 17
102,00
21 10W 22 15W 23 L4
1 1 1 1
1 1
1
1
1
0
0,00
0
0,00
21
89,25
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
24 0,75W 1 1 1 3
2,25
25 1,5W 1 1 2
3,00
26 3W 1 1 1 1 4
12,00
27 6W 1 12
72,00
28 10W 0
0,00
29 15W 0
0,00
30 L5
22
92,25
1 1 1 1 1
1
1
1
1
1
1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
31 0,75W 32 1,5W 1 1 33 3W 1 1 34 6W 1 1 1 1 1 35 10W 36 15W 1 1 1 1 1
0,75
3
4,50
1 7
21,00
1 11
66,00
1 1
1 1 0
0,00
0
0,00
8
1
1
1
37 20W 38 L6
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
39 0,75W 1 40 1,5W 41 3W 1 1 1 1 1 1 1 42 6W 1 43 10W 44 15W 45 L7
0
0,00
27
103,50
1 2
1,50
0
0,00
1 1 16
48,00
1 9
54,00
1 1 1 1
1 1 1 1 1 1 1
1 1 1 0
0,00
0
0,00
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
20
108,00
46 0,75W 0
0,00
47 1,5W 0
0,00
48 3W 1 4
12,00
49 6W 1 1 1 1 1 1 1 1 1 1 16
96,00
50 10W 0
0,00
51 15W 0
0,00
52 L8
33
105,75
1 1 1 1 1 1 1 1 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
53 0,75W 54 1,5W 55 3W 56 6W 1 1 1 1 1 1 1 1 1 57 10W 58 15W 59 L9
60 1 1 1 1
1
1
1
1
1
1 1 1 1 1 1 1 3 5
3,75
1 10
15,00
1 7
21,00
11
66,00
1 1 0
0,00
0
0,00
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
4
50,00
3W 0
0,00
61 6W 0
0,00
62 10W 1 1 2
20,00
63 15W 1 1 2
30,00
64 L10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
14
210,00
65 6W 0
0,00
66 10W 0
0,00
67 15W 1 1 1 1 1 1 1 1 1 1 14
210,00
68 L11
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
14
181,00
69 6W 70 10W 71 15W 1 1 1 1 1 1 1 1 1 72 L12
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
73 6W 74 10W 1 1 75 15W 1 1 1 1 1 1 1 1 76 L13
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
77 6W 78 10W 1 1 1 1 1 1 1 1 1 1 1 1 1
6,00
1 4
40,00
9
135,00
14
200,00
0
0,00
2
20,00
12
180,00
16
190,00
1 1 1 1 1 1 1 1
1 1
0
0,00
1 10
100,00
9
79 15W 1 1 1 1 1 80 L14
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
81 6W 82 10W 1 83 15W 1 1 1 1 1 1 1 1 84 L15
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
85 6W 86 10W 1 1 1 1 87 15W 1 1 1 1 1 88 L16
89 90 91 92 93 94 95 1 6
90,00
14
200,00
0
0,00
1 2
20,00
1 12
180,00
17
205,00
1 1 0
0,00
1 10
100,00
1 7
105,00
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
7
105,00
6W 0
0,00
10W 0
0,00
15W 1 1 1 1 1 1 1 7
105,00
L17
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
11
115,00
6W 10W 1 1 1 1 1 1 1 1 15W 1 96 L18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
97 3W 1 1 98 6W 99 10W 100 15W 1 1 1 1 1 1 1 1 101 L19
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
102 6W 103 10W 1 1 1 1 1 1 1 1 104 15W 1 105 L20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
106 6W 107 10W 1 1 108 15W 1 1 1 1 1 1 1 109 L21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
1 1 1 1 1
1
0
0,00
1 10
100,00
1
15,00
13
171,00
2
6,00
0
0,00
0
0,00
11
165,00
10
105,00
1 1 1 1 1 0
0,00
1 9
90,00
1
15,00
14
195,00
1 1 1 1 0
0,00
1 3
30,00
11
165,00
4
50,00
110 12,5W 1 1 1 1 4
50,00
111 10W 0
0,00
112 15W 0
0,00
113 L22
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
3
37,50
114 12,5W 1 1 1 3
37,50
115 10W 0
0,00
116 15W 0
0,00
117 L23
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
4
50,00
118 12,5 1 1 1 1 4
50,00
119 10W 0
0,00
120 15W 0
0,00
10
121 L24
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
7
87,50
122 12,5 1 1 1 1 1 1 1 7
87,50
123 10W 0
0,00
124 15W 0
0,00
125 Liczba głośników
126 Moc wyliczona
W
2960,50
127 Moc gwarantowana
W
3840,00
128 Moc rezerwowa
W
879,50
2.3
370 2960,50
Projekt Akustyczny.
Dla zwykłego użytkowania pomieszczeń hali przyjęto typowe wartości poziomu
hałasu (na poziomie 70dB) występujące w poszczególnych częściach budynku wraz
z zalecanymi normą poziomami komunikatu i współczynnika zrozumiałości mowy
RASTI.
Na potrzeby niniejszego projektu przyjęto wartości przekroczenia poziomu tła w
przedziale 6-20 dB (według zaleceń normy PN-EN 60849). Powyższe wartości
należy osiągnąć odpowiednim ustawianiem mocy odczepowej poszczególnych
głośników, w zależności od wielkości i aranżacji pomieszczenia. Na rzutach
kondygnacji głośniki zostały umieszczone w sposób odpowiedni do poziomu hałasu
w pomieszczeniach oraz kąta pokrycia, uwzględniając odbicia od powierzchni.
Ogólny widok akustyczny hali wystawienniczej pokazuje poniższy rysunek.
11
Po wykonaniu instalacji systemu DSO należy dokonać pomiarów wartości impedancji
linii głośnikowych oraz wynikające z tych pomiarów moce wynikowe linii i otrzymane
protokoły załączyć do dokumentacji powykonawczej niniejszego systemu. Również
należy wykonać pomiary zrozumiałości mowy RASTI oraz ciśnienia akustycznego
[dB(A)].
2.4
Projekt elektroakustyczny.
Projektowany Dźwiękowy System Ostrzegawczy jest oparty o urządzenia systemu
Venas firmy Ambient System oraz głośniki typu matryce linowe i projektorowe o
zadanych charakterystykach, które powinny
posiadać certyfikaty CNBOP. W
systemie wykorzystano wzmacniacze mocy 2x120W oraz 1x240W, jako
wzmacniacze podstawowe oraz jeden wzmacniacz rezerwowy 240W. Do symulacji
akustycznej komputerowej hali wykorzystano kolumny liniowe oraz projektory
dźwiękowe.
2.5
Pamięć komunikatów.
Jednostka centralna systemu będzie wyposażona jest w kartę pamięci typu Flash o
pojemności 64MB. Komunikaty powinny być dostarczone wraz z systemem DSO
przez jego producenta.
2.6
System zasilania dedykowanego.
Projektuje się zainstalowanie osprzętu systemu DSO w szafach rack 19" o wysokości
42U zlokalizowanych w pomieszczeniu ochrony (pom. nr 0.14). Szafy będą
wyposażona w baterie podtrzymujące zasilanie umożliwiające działanie systemu
przez 24 godziny w stanie czuwania, oraz przez 30 minut w stanie emisji
komunikatów o pełnej mocy.
Elementy aktywne systemu będą rozmieszczone w trzech szafach oznaczona CDSO
Nr-1, Nr-2 i nr-3 i będą zawierały:
12
1 ABT-V2000
Menadżer systemu
1
2 ABT-V200MWM
ABT-V200PZG +
3
EVCE128Q
4 ABT-V200RMS
Moduł wejściowy mikrofonu
8
Płyta zapowiedzi głosowych + karta pamięci
2
Rozszerzony Mikrofon strażaka
1
5 ABT-V200MS
Mikrofon strażaka
2
6 ABT-V200M
Mikrofon strefowy
7
7 ABT-V210RM
Rozszerzenie mikrofonu
6
8 ABT-WB-RM200
Ścienny uchwyt pulpitów mikrofonowych
4
9 ABT-V2000JK
Jednostka kontroli
10 ABT-V200IMK2
Impedancyjny moduł kontroli 2 linii głośnikowych
11 ABT-V2122WM
Wzmacniacz mocy 2x120W 100V
3
24
9
12 ABT-V2241WM
Wzmacniacz mocy 240W 100V
10
13 ABT-V200MWW
Moduł wejściowy wzmacniacza mocy
23
14 VP-200VX-BGM
Moduł wejściowy wzmacniacza mocy+ BGM
15 ABT-V2000RZ
Rama zasilaczy
3
16 ABT-V200Z
Zasilacz
9
4
17 ABT-V2000JZ
Jednostka zarządzająca systemem zasilania
3
18 ABT-SMS
Skrzynka wyniesionego mikrofonu strażaka
3
19 ABT-V200SAP
Interfejs między SAP i DSO
Szafa systemu DSO, okablowana, z 2 akumulatorami 160
Ah
Szafa systemu DSO, okablowana, z 2 akumulatorami 120
Ah
1
20 RACK 42U
21 RACK 42U
1
2
Szafy DSO będą zasilane z rozdzielnicy głównej obiektowej przewodem HDGs
5x6mm2 H90. W szafach DSO są umieszczone niezależne wyłączniki prądu.
Integracja centrali CDSO z centralą istniejącą CDSO-1 odbywać się będzie po
zaprojektowanym w projekcie podstawowym kablu sygnałowym. Centralą nadrzędna
będzie central nowo projektowana.
2.7
Współpraca z centralą CSP.
Współpraca z centralą sygnalizacji pożaru CSP będzie odbywać się bezpośrednio
kablem łącznikowych pomiędzy obiema centralami: CSP i CDSO..
Emitowane w trakcie pożaru słowne komunikaty ewakuacyjne zastaną dostarczone
przez osobę odpowiedzialną za bezpieczeństwo pożarowe obiektu lub otrzymane od
producenta systemu.
2.8
Okablowanie.
Urządzenia aktywne systemu zostaną połączone w sieć przy pomocy dedykowanego
okablowania.
Linie głośnikowe będą wykonane certyfikowanymi przez CNBOP przewodami HDGs
2x2,5mm2 lub 2x4mm2 firmy Bitner.
• Przewody sygnałowe z centrali CDSO wyprowadzić na korycie klasy E90 o
statusie certyfikowanej trasy kablowej. W hali wystawienniczej przewody
sygnałowe należy ułożyć natynkowo na wcześniej przygotowanych trasach na
ścianach i stropach hali przymocowane certyfikowanymi uchwytami. Przebicia
przez stropy i ściany uszczelnić masą uszczelniającą np. typu SOUDAFOAM
FR.
• Projektowane linie głośnikowe stanowią strukturę otwartej pętli.
13
• Niezbędne połączenia linii głośnikowych wykonywać z użyciem dedykowanych
certyfikowanych metalowych puszek np. typu PIP.
• Mikrofony strefowe i mikrofon strażaka w pomieszczeniu ochrony należy
połączyć z modułami wejściowymi kablami STP 4x2x0,5mm kat. 5e.
• Mikrofony strefowe w dużej odległości mogą wymagać miejscowego zasilacza.
• Mikrofony strażaka wyniesione (poza pom. ochrony) połączyć kablami
HTKSHekw 4x2x0,8mm PH90, przy czym dla rozszerzonego mikrofonu
strażaka należy ułozyc dodatkowo drugi przewód do istniejącej szafy DSO
HTKSHekw 4x2x1,4mm PH90.
• Pomiędzy szafą z etapu I i szafą z etapu II należy przewidzieć przewód
HTKSH 2x2x0,8mm PH90 dla przekazywania pomiędzy systemami informacji
o ewentualnym uszkodzeniu systemu.
• Dodatkowo należy poprowadzić linię kablową z szafy DSO przewodem
HTKSH 1x2x1,4mm do modułów DSC lub innych elementów odłączających
dedykowany sprzęt nagłaśniający w poszczególnych salach seminaryjnych i
konferencyjnych o ile takie urządzenia nagłaśniające będą zainstalowane.
2.9
Głośniki.
2.9.1. Głośniki typy i modele.
Dobór głośników został przeprowadzony spośród urządzeń posiadających certyfikat
do stosowania w dźwiękowych systemach ostrzegawczych. W nagłośnieniu
pomieszczeń objętych niniejszym opracowaniem zostały wzięte pod uwagę głośniki
projektorowe i kolumnowe. Zestawienie modeli głośników zostało przedstawione w
Tabeli nr 2.
Tabela nr 2. Zestawienie modeli głośników.
Rodzaj
projektorowy
kolumnowy
sufitowy
naścienny
Producent
Partner
Bosch
Partner
Partner
Model
DAW 130/20 PP
LBC 3210
DELF 165/6 PP
WAC 165/6 PP1
Moc (odczepy)
20W (5/10/20)
60W (15/30/60)
6W (1,5/3/6)
6W (0,75/1,5/3/6)
2.9.2. Charakterystyka głośników.
Głośniki DSO zostały zamodelowane z uwzględnieniem wysterowania oraz
charakterystyk kierunkowych i częstotliwościowych. Poniżej podane zostały
przykładowe charakterystyki głośników dla wybranych częstotliwości.
14
DAW 130/20 Charakterystyka kierunkowa 500Hz
DAW 130/20 Charakterystyka kierunkowa 1kHz
DAW 130/20 Charakterystyka kierunkowa 2kHz
DAW 130/20 Charakterystyka częstotliwościowa
LBC3210 Charakterystyka kierunkowa 500Hz
LBC3210 Charakterystyka kierunkowa 1kHz
LBC3210 Charakterystyka kierunkowa 2kHz
LBC3210 Charakterystyka częstotliwościowa
15
DELF 165/6 Charakterystyka kierunkowa 500Hz
DELF 165/6 Charakterystyka kierunkowa 1kHz
DELF 165/6 Charakterystyka kierunkowa 2kHz
DELF 165/6 Charakterystyka częstotliwościowa
WAC 165/6 Charakterystyka kierunkowa 500Hz
WAC 165/6Charakterystyka kierunkowa 1kHz
WAC 165/6Charakterystyka kierunkowa 2kHz
WAC 165/ Charakterystyka częstotliwościowa
16
2.9.3. Parametry akustyczne.
Rozmieszczenie i moc głośników dobrano tak, aby poziom ciśnienia akustycznego
(SPL) na poziomie uszu słuchacza przekraczał co najmniej o 10dB poziom tła, a
współczynnik zrozumiałości mowy wynosił minimum 0,5 RASTI. W przypadku
nieuzyskania założonego poziomu RASTI w danym pomieszczeniu należy tak
zaadaptować to pomieszczenie (montaż firanek, wertikali, wykładziny podłogowe i
ścienne), aby współczynnik RASTI wzrósł co najmniej do poziomu 0,5. Powyższa
adaptacja nie jest przedmiotem niniejszego projektu, a tylko wskazówką dla
Inwestora.
2.9.4. Zastrzeżenie projektowe.
Przeprowadzona analiza akustyczna z wykorzystaniem symulacji komputerowej
dotyczy ściśle warunków znanych i przyjętych przy jej wykonywaniu. Należy mieć na
uwadze, że każda zmiana założeń technicznych dotyczących geometrii, wystroju
oraz wyposażenia pomieszczeń może spowodować zmianę warunków akustycznych,
w tym wskaźników zrozumiałości otrzymanych w symulacji i pogorszyć komfort
akustyczny odczuwany przez słuchaczy. W takim przypadku należy ponowić
przeprowadzenie symulacji lub weryfikować spełnienie wymagań i oczekiwań na
drodze pomiarów oraz odsłuchu.
2.9.4. Lokalizacja szczegółowa głośników.
Głośniki naścienne będą zamocowane na ścianach właściwych za pomocą kotew
stalowych np. produkcji OBO Bettermann. Montażu dokonać zgodnie z instrukcją
producenta.
W pomieszczeniach i korytarzach gdzie znajdują się sufity podwieszane
zaprojektowano głośniki sufitowe montowane w suficie podwieszonym (i
przytwierdzone linka stalową do sufitu właściwego).
Z uwagi na przeznaczenie obiektu przyjęto, że średni poziom hałasu występujący w
projektowanym budynku wynosił będzie 70dB.
Z uwagi na charakter nagłaśnianych przestrzeni i sposób wykończenie pomieszczeń
zaprojektowano następujące typy głośników:
• głośniki – zestawy matryc liniowych naściennych montowanych na ścianach i
słupach zlokalizowanych w hali na wysokości 3,5m od posadzki i z kątem
nachylenia zgodnym z Tabelą 3.,
• głośniki projektorowe sufitowe na pionowych certyfikowanych zawiesiach
zamocowanych do sufitu dachowego zawieszone na wysokości 5,50m nad
posadzką hali.
Tabela 3. Lokalizacja wraz z ustawieniami głośników.
Tabela 3.1 hala A1.
Lp
1
2
3
Nr
A1_L12/05
A1_L12/06
A1_L12/07
Model
LBC 3210/00
LBC 3210/00
LBC 3210/00
Moc [W]
15,0
15,0
15,0
X [m]
56,35
75,85
98,35
17
Y [m]
165,70
165,70
165,70
Z [m]
3,50
3,50
3,50
Hor [°]
0
0
0
Ver [°]
-8
-8
-8
Rot [°]
0
0
0
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
A1_L12/09
A1_L12/08
A1_L12/04
A1_L12/13
A1_L12/10
A1_L12/12
A1_L12/14
A1_L12/11
A1_L12/03
A1_L13/5
A1_L13/6
A1_L13/8
A1_L13/7
A1_L12/02
A1_L13/4
A1_L13/2
A1_L13/3
A1_L13/9
A1_L13/1
A1_L12/01
A1_L13/11
A1_L13/10
A1_L13/13
A1_L13/12
A1_L13/15
A1_L13/14
A1_L13/16
DAW 130/20 PP
DAW 130/20 PP
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
DAW 130/20 PP
DAW 130/20 PP
DAW 130/20 PP
DAW 130/20 PP
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
DAW 130/20 PP
DAW 130/20 PP
DAW 130/20 PP
DAW 130/20 PP
DAW 130/20 PP
DAW 130/20 PP
LBC 3210/00
Razem moc [W]
10,0
10,0
15,0
15,0
15,0
15,0
15,0
15,0
15,0
10,0
10,0
10,0
10,0
15,0
15,0
15,0
15,0
15,0
15,0
15,0
10,0
10,0
10,0
10,0
10,0
10,0
15,0
91,35
100,35
50,45
75,85
75,30
76,40
105,30
75,85
50,45
91,35
100,35
91,35
100,35
50,45
75,85
75,30
76,40
105,30
75,85
50,45
91,35
100,35
91,35
100,35
91,35
100,35
75,85
146,30
146,30
143,80
136,80
136,30
136,30
136,30
135,80
128,80
126,30
126,30
116,30
116,30
113,80
106,80
106,30
106,30
106,30
105,80
98,80
96,30
96,30
87,30
87,30
78,30
78,30
76,80
5,50
5,50
3,50
3,50
3,50
3,50
3,50
3,50
3,50
5,50
5,50
5,50
5,50
3,50
3,50
3,50
3,50
3,50
3,50
3,50
5,50
5,50
5,50
5,50
5,50
5,50
3,50
X [m]
159,10
114,10
136,60
113,60
122,60
166,00
136,60
107,10
136,00
137,15
136,60
166,50
113,60
122,60
113,60
122,60
166,00
136,60
107,10
136,00
137,15
136,60
166,00
112,10
121,10
112,10
121,10
112,10
121,10
136,60
137,10
Y [m]
166,20
165,70
165,70
146,30
146,30
143,80
136,80
136,30
136,30
136,30
135,80
128,80
126,30
126,30
116,30
116,30
113,80
106,80
106,30
106,30
106,30
105,80
98,80
96,30
96,30
87,30
87,30
78,30
78,30
76,80
75,95
Z [m]
3,50
3,50
3,50
5,50
5,50
3,50
3,50
3,50
3,50
3,50
3,50
3,50
5,50
5,50
5,50
5,50
3,50
3,50
3,50
3,50
3,50
3,50
3,50
5,50
5,50
5,50
5,50
5,50
5,50
3,50
3,50
0
0
90
180
-90
90
-90
0
90
0
0
0
0
90
180
-90
90
-90
0
90
0
0
0
0
0
0
180
-90
-90
-8
-8
-8
-8
-8
-8
-8
-90
-90
-90
-90
-8
-8
-8
-8
-8
-8
-8
-90
-90
-90
-90
-90
-90
-8
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Hor [°]
0
0
0
0
0
-90
180
90
-90
90
0
-90
0
0
0
0
-90
180
90
-90
90
0
-90
0
0
0
0
0
0
180
90
Ver [°]
-8
-8
-8
-90
-90
-8
-8
-8
-8
-8
-8
-8
-90
-90
-90
-90
-8
-8
-8
-8
-8
-8
-8
-90
-90
-90
-90
-90
-90
-8
-8
Rot [°]
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
390,0
Tabela 3.2 Hala A2.
Lp
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Nr
A2_L14/05
A2_L14/07
A2_L14/06
A2_L14/08
A2_L14/09
A2_L14/04
A2_L14/10
A2_L14/14
A2_L14/13
A2_L14/11
A2_L14/12
A2_L14/03
A2_L15/6
A2_L15/5
A2_L15/7
A2_L15/8
A2_L14/02
A2_L15/4
A2_L15/9
A2_L15/1
A2_L15/3
A2_L15/2
A2_L14/01
A2_L15/10
A2_L15/11
A2_L15/12
A2_L15/13
A2_L15/14
A2_L15/15
A2_L15/16
A2_L15/17
Model
LBC 3210/00
LBC 3210/00
LBC 3210/00
DAW 130/20 PP
DAW 130/20 PP
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
DAW 130/20 PP
DAW 130/20 PP
DAW 130/20 PP
DAW 130/20 PP
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
DAW 130/20 PP
DAW 130/20 PP
DAW 130/20 PP
DAW 130/20 PP
DAW 130/20 PP
DAW 130/20 PP
LBC 3210/00
LBC 3210/00
Moc [W]
15,0
15,0
15,0
10,0
10,0
15,0
15,0
15,0
15,0
15,0
15,0
15,0
10,0
10,0
10,0
10,0
15,0
15,0
15,0
15,0
15,0
15,0
15,0
10,0
10,0
10,0
10,0
10,0
10,0
15,0
15,0
18
Razem moc [W]
405,0
Tabel 3 Hala B1.
Lp
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Nr
B1_L18/11
B1_L17/10
B1_L17/11
B1_L17/8
B1_L17/9
B1_L18/12
B1_L18/13
B1_L17/6
B1_L17/7
B1_L18/9
B1_L18/10
B1_L18/8
B1_L17/5
B1_L18/7
B1_L17/3
B1_L17/4
B1_L18/1
B1_L17/2
B1_L17/1
B1_L18/3
B1_L18/2
B1_L18/4
B1_L18/5
B1_L18/6
Model
LBC 3210/00
DAW 130/20 PP
DAW 130/20 PP
DAW 130/20 PP
DAW 130/20 PP
LBC 3210/00
LBC 3210/00
DAW 130/20 PP
DAW 130/20 PP
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
DAW 130/20 PP
DAW 130/20 PP
LBC 3210/00
DAW 130/20 PP
DAW 130/20 PP
DELF 165/6 PP
DELF 165/6 PP
LBC 3210/00
LBC 3210/00
LBC 3210/00
Razem moc [W]
Moc [W]
15,0
10,0
10,0
10,0
10,0
15,0
15,0
10,0
10,0
15,0
15,0
15,0
15,0
15,0
10,0
10,0
15,0
10,0
10,0
3,0
3,0
15,0
15,0
15,0
X [m]
75,85
95,55
103,55
95,55
103,55
56,35
63,35
95,55
103,55
75,85
75,30
76,40
105,35
75,85
95,55
103,55
63,25
95,55
103,55
53,35
59,55
50,45
69,35
90,85
Y [m]
59,30
55,10
55,10
45,10
45,10
43,50
43,00
35,10
35,10
23,35
22,80
22,80
22,80
22,25
13,30
13,30
7,80
4,30
4,30
3,78
3,78
-6,95
-13,60
-13,60
Z [m]
3,50
6,00
6,00
5,50
5,50
3,50
3,50
5,50
5,50
3,50
3,50
3,50
3,50
3,50
5,50
5,50
3,50
5,50
5,50
2,90
2,90
3,50
3,50
3,50
Hor [°]
0
0
0
0
0
180
90
0
0
180
-90
90
-90
0
0
0
90
0
0
0
0
90
180
180
Ver [°]
-8
-90
-90
-90
-90
-8
-8
-90
-90
-8
-8
-8
-8
-8
-90
-90
-8
-90
-90
-90
-90
-8
-8
-8
Rot [°]
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
X [m]
136,60
110,90
118,90
126,90
166,00
110,90
118,90
166,00
110,90
118,90
136,60
107,10
136,05
137,15
166,00
136,60
110,90
118,90
166,00
110,90
118,90
110,90
121,60
144,10
Y [m]
59,30
55,10
55,10
55,10
52,55
45,10
45,10
37,80
35,10
35,10
23,35
22,80
22,80
22,80
22,80
22,25
13,30
13,30
7,80
4,30
4,30
-4,70
-13,60
-15,10
Z [m]
3,50
5,50
5,50
5,50
3,50
5,50
5,50
3,50
5,50
5,50
3,50
3,50
3,50
3,50
3,50
3,50
5,50
5,50
3,50
5,50
5,50
5,50
3,50
3,50
Hor [°]
0
0
0
0
-90
0
0
-90
0
0
180
90
-90
90
-90
0
0
0
-90
0
0
0
180
180
Ver [°]
-8
-90
-90
-90
-8
-90
-90
-8
-90
-90
-8
-8
-8
-8
-8
-8
-90
-90
-8
-90
-90
-90
-8
-8
Rot [°]
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
286,0
Tabela 3.4 Hala B2.
Lp
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Nr
B2_L20/7
B2_L19/10
B2_L19/9
B2_L19/8
B2_L20/8
B2_L19/7
B2_L19/6
B2_L20/9
B2_L19/5
B2_L19/4
B2_L20/5
B2_L19/3
B2_L20/6
B2_L20/4
B2_L20/10
B2_L20/3
B2_L19/2
B2_L19/1
B2_L20/11
B2_L20/1
B2_L20/2
B2_L20/14
B2_L20/13
B2_L20/12
Model
LBC 3210/00
DAW 130/20 PP
DAW 130/20 PP
DAW 130/20 PP
LBC 3210/00
DAW 130/20 PP
DAW 130/20 PP
LBC 3210/00
DAW 130/20 PP
DAW 130/20 PP
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
DAW 130/20 PP
DAW 130/20 PP
LBC 3210/00
DAW 130/20 PP
DAW 130/20 PP
DAW 130/20 PP
LBC 3210/00
LBC 3210/00
Moc [W]
15,0
10,0
10,0
10,0
15,0
10,0
10,0
15,0
10,0
10,0
15,0
15,0
15,0
15,0
15,0
15,0
10,0
10,0
15,0
10,0
10,0
10,0
15,0
15,0
19
Razem moc [W]
300,0
Tabela 3.5 Łącznik.
Lp
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Nr
L_L11/6
L_L11/7
L_L11/8
L_L11/9
L_L11/10
L_L11/11
L_L11/14
L_L11/13
L_L11/12
L_L10/14
L_L11/1
L_L11/5
L_L11/2
L_L11/4
L_L11/3
L_L10/13
L_L9/4
L_L9/3
L_L9/2
L_L10/12
L_L9/1
L_L10/11
L_L10/10
L_L10/8
L_L10/9
L_L10/7
L_L10/2
L_L10/6
L_L10/5
L_L10/4
L_L10/3
L_L10/1
Model
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
DAW 130/20 PP
DAW 130/20 PP
WAC 165/6 PP1
DAW 130/20 PP
DAW 130/20 PP
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
DAW 130/20 PP
DAW 130/20 PP
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
Razem moc [W]
Moc [W]
15,0
15,0
15,0
15,0
10,0
10,0
6,0
10,0
10,0
15,0
15,0
15,0
15,0
15,0
15,0
15,0
15,0
10,0
10,0
15,0
15,0
15,0
15,0
15,0
15,0
15,0
15,0
15,0
15,0
15,0
15,0
15,0
X [m]
4,68
14,68
24,68
34,68
41,25
47,25
49,45
41,25
47,25
4,68
44,68
24,32
25,04
24,32
25,04
4,68
44,68
24,68
24,68
4,68
44,68
24,32
25,04
24,32
25,04
4,68
44,68
4,68
14,68
24,68
34,68
44,68
Y [m]
59,95
59,95
59,95
59,95
57,20
57,20
54,76
52,30
52,30
43,55
43,55
43,41
43,41
42,69
42,69
42,55
42,55
34,65
26,45
18,55
18,55
18,41
18,41
17,69
17,69
17,55
17,55
1,15
1,15
1,15
1,15
1,15
Z [m]
-1,50
-1,50
-1,50
-1,50
1,20
4,70
-2,00
1,20
4,70
-1,50
-1,50
-1,50
-1,50
-1,50
-1,50
-1,50
-1,50
1,00
1,00
-1,50
-1,50
-1,50
-1,50
-1,50
-1,50
-1,50
-1,50
-1,50
-1,50
-1,50
-1,50
-1,50
Hor [°]
0
0
0
0
0
0
-90
0
0
180
180
-135
135
-45
45
0
0
0
0
180
180
-135
135
-45
45
0
0
180
180
180
180
180
Ver [°]
-8
-8
-8
-8
-90
-90
0
-90
-90
-8
-8
-8
-8
-8
-8
-8
-8
-90
-90
-8
-8
-8
-8
-8
-8
-8
-8
-8
-8
-8
-8
-8
Rot [°]
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
441,0
Tabela 3.6 Pasaż.
Lp
1
2
3
4
5
6
7
Nr
P_L16/1
P_L16/7
P_L16/2
P_L16/3
P_L16/4
P_L16/5
P_L16/6
Model
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
LBC 3210/00
Razem moc [W]
Moc [W]
15,0
15,0
15,0
15,0
15,0
15,0
15,0
X [m]
49,95
158,55
75,85
90,85
106,22
121,60
136,60
Y [m]
68,05
68,00
61,05
61,05
61,05
61,05
61,05
Z [m]
3,50
3,50
3,50
3,50
3,50
3,50
3,50
Hor [°]
90
-90
180
180
180
180
180
Ver [°]
-8
-8
-8
-8
-8
-8
-8
Rot [°]
0
0
0
0
0
0
0
105,0
Głośniki naścienne nadają się do nagłaśniania przestrzeni otwartych jak i korytarzy
oraz umożliwiają uzyskanie odpowiedniej wartość ciśnienia dźwięku przy zadanym
kącie pokrycia i odpowiednio dobranej odległości między głośnikami. Głośniki te
zostały zaprojektowane z myślą o budynkach, w których jakość działania systemu
słownych alarmów ewakuacyjnych określona jest specjalnymi przepisami. Spełniają
20
one polską normę EN 60065 oraz brytyjską BS5839 część 8. Głośniki sufitowe
zostaną zamontowane nad ścieżkami/drogami komunikacyjnymi hali zgodnie z
aranżacją zagospodarowania powierzchni wystawienniczych.
Zastosowane głośniki posiadają możliwość regulacji mocy wyjściowej poprzez cztery
odczepy na uzwojeniu pierwotnym transformatora (moc znamionowa, połowa tej
mocy, ćwiartka lub jedna ósma tej mocy). Nastawy mocy poszczególnych głośników
oraz ich rozmieszczenie zostały dobrane indywidualnie w zależności od warunków
panujących w przestrzeniach przez nie nagłaśnianych co wykazała symulacja
akustyczna.
W przypadku głośników montowanych do ścian należy mocować je przy pomocy
kołków metalowych. Kable do wszystkich typów głośników należy wprowadzać
poprzez dławice kablowe zgodnie z wymaganiami certyfikacji głośników.
W przypadku łączenia dwóch kabli w jednym punkcie należy bezwzględnie wykonać
połączenie ich za pomocą tulei zaciskowych w puszkach typu PIP.
Karty katalogowe zastosowanych w projekcie głośników zostały zamieszczone na
końcu opracowania.
2.10. Dobór linii głośnikowych.
W zależności od długości linii głośnikowych konieczne jest zastosowanie kabli o
odpowiednich przekrojach dostosowanych do przesyłanej mocy. Tabela nr 4 zawiera
zaprojektowane typy kabli na realizację poszczególnych linii głośnikowych.
Tabela nr 4.
Strefa 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Nr linii Obszar nagłaśniany Poziomy L1 Pomieszczenia obsługi ‐500 L2 Pomieszczenia obsługi ‐500 L3 Pomieszczenia techniczne ‐500 Pomieszczenia ogólnodostępne +0,00 L4 Pomieszczenia techniczne +350 Pomieszczenia ogólnodostępne +0,00 L5 Pomieszczenia techniczne +350 Pomieszczenia ogólnodostępne +0,00 L6 Pomieszczenia techniczne +350 Pomieszczenia techniczne +910 L7 Pomieszczenia techniczne +910 Pomieszczenia ogólnodostępne +0,00 L8 Pomieszczenia techniczne +350 Pomieszczenia techniczne +910 L9 Kawiarnia ‐500 L10 Łącznik ‐500 L11 Łącznik ‐500 L12 Hala A Część A1 (Lewa) +0,00 L13 Hala A Część A1 (Lewa) +0,00 L14 Hala A Część A2 (Prawa)) +0,00 L15 Hala A Część A2 (Prawa)) +0,00 21
Typ kabla linii głośnikowej ilość [m] 253 273 306 HDGs PH90/H90 HDGs 2x2,5mm2 HDGs 2x2,5mm3 HDGs 2x2,5mm4 180 HDGs 2x2,5mm2 198 HDGs 2x2,5mm2 328 HDGs 2x2,5mm2 191 HDGs 2x2,5mm2 412 HDGs 2x4mm3 149 350 378 466 546 496 548 HDGs 2x2,5mm2 HDGs 2x2,5mm2 HDGs 2x2,5mm2 HDGs 2x2,5mm2 HDGs 2x2,5mm2 HDGs 2x2,5mm2 HDGs 2x2,5mm2 16 17 18 19 20 21 22 23 24 L16 L17 L18 L19 L20 L21 L22 L23 L24 Pasaż Hala B Część B1 (Lewa) Hala B Część B1 (Lewa) Hala B Część B2 (Prawa)) Hala B Część B2 (Prawa)) Parkingi ‐ Eleacja południowa Parkingi ‐ Eleacja wschodnia Parkingi ‐ Eleacja wschodnia Parkingi ‐ Eleacja północna +0,00 +0,00 +0,00 +0,00 +0,00 +0,00 +0,00 +0,00 +0,00 330 450 380 400 484 298 240 320 464 HDGs 2x2,5mm2 HDGs 2x2,5mm2 HDGs 2x2,5mm2 HDGs 2x2,5mm2 HDGs 2x2,5mm2 HDGs 2x2,5mm2 HDGs 2x2,5mm2 HDGs 2x2,5mm2 HDGs 2x2,5mm2 2.11. Moduły kontroli linii.
System należy wyposażyć w moduły kontroli impedancji linii głośnikowej, które to
moduły montuje się we wzmacniaczach oraz na końcach linii głośnikowych za
ostatnim głośnikiem. Moduł za ostatnim głośnikiem musi być zamocowany w
obudowie z blachy stalowej firmy Kabe typu KB-0251, o wymiarach 147x85x28,
wyposażonej w kostkę ceramiczną z bezpiecznikiem topikowym. Obudowę mocować
przy pomocy kołków rozporowych stalowych atestowanych.
2.12. Dobór wzmacniaczy mocy.
Poszczególne linie głośnikowe posiadają różną liczbę dołączonych do nich
głośników, a co za tym idzie charakteryzują się różnym zapotrzebowaniem na moc.
Szczegółowy przydział mocy ilustruje Tabela 1. W budowanym systemie
zastosowano dwa typy wzmacniaczy: 2x120W oraz 1x240W. System DSO będzie
zawierał liczbę wzmacniaczy wyspecyfikowaną w zestawieniu materiałowym.
2.13. Pomieszczenie centrali DSO.
Pomieszczeniem centrali DSO jest wydzielone pożarowo pomieszczenie ochrony, w
którym będzie zlokalizowana szafa CDSO. Przy stojaku centrali CDSO zlokalizowana
będzie stacja mikrofonowa administratora. Stacja wywoławcza mikrofonowa strażaka
oraz informacyjna wyniesiona stacja mikrofonowa z dwoma modułami rozszerzeń
zlokalizowane będą zgodnie z rysunkami DSO-2 i DSO-3.
2.14. Drabinka priorytetów.
Najwyższy priorytet w systemie
posiada mikrofon strażaka umieszczony w
dedykowanej szafce; następnie - sygnały sterujące z centrali SAP (dla wyzwolenia
emisji komunikatów audio w DSO), natomiast najniższy priorytet posiada wyniesiona
stacja mikrofonowa.
Dowódca akcji ratowniczej będzie mógł przerwać automatyczną emisję komunikatów
i przekazać swoje instrukcje przy wykorzystaniu pulpitu strażaka bądź przy
wykorzystaniu pulpitu użytkownika kierując instrukcje do wybranych stref za pomocą
dołączonych klawiatur.
2.15. Dokumenty związane z DSO.
Wykonawca systemu zobowiązany jest do dostarczenia Inwestorowi:
- dokumentacji powykonawczej;
- instrukcji obsługi;
- dziennika operacyjnego;
22
- instrukcji konserwacji.
2.15.1. Dokumentacja powykonawcza
Powinna zawierać dokładną lokalizację poszczególnych elementów systemu DSO,
oraz protokoły pomiarów funkcjonowania zainstalowanego systemu, łączenie z:
• pomiarami głośników obciążonych przez układ w trybie zagrożenia;
• opisem ustawienia każdego regulowanego elementu systemu, łącznie z
poziomem wyjściowym wzmacniaczy mocy;
• pomiarami poziomów ciśnienia dźwięku;
• pomiarami poziomów zrozumiałości.
2.15.2. Instrukcja obsługi
Powinna być aktualizowana po modyfikacjach lub uzupełnieniach systemu. Instrukcja
taka powinna zawierać:
• funkcjonalne działanie systemu,
• czynności, które podejmuje się w przypadku uszkodzenia systemu.
Wykonawca systemu powinien także dołączyć związane z instrukcją kopie instrukcji
eksploatacyjnych.
2.15.3. Dziennik pracy systemu
Wykonawca powinien dostarczyć Dziennik pracy systemu oprawiony w sztywnych
okładkach, który powinien być przechowywany przez cały okres eksploatacji systemu
i powinien stanowić pełny zapis dotyczący użytkowania systemu i okoliczności
wszystkich uszkodzeń, wraz ze wszystkimi wykonanymi automatycznie zapisami,
włączając w to:
- daty i czasy użytkowania systemu;
- szczegóły sprawdzeń i wykonane badania okresowe;
- czas i datę wystąpienia każdego uszkodzenia;
- szczegóły znalezienia uszkodzenia i okoliczności jego znalezienia (na przykład
podczas okresowej konserwacji);
- działania prowadzące do usunięcia usterki lub wykonania naprawy;
- datę, czas i nazwisko osoby odpowiedzialnej za obsługę systemu;
- podpis osoby odpowiedzialnej, jeśli zdarzyło się jakiekolwiek uszkodzenie lub
zostało ono naprawione.
2.15.4. Instrukcje konserwacji
Instrukcje dotyczące konserwacji (w sztywnych okładkach), w których podane będą
szczegóły wszystkich prac wymaganych do konserwacji instalacji i sprzętu, we
właściwym porządku ich wykonywania, zawierające określone kryteria
funkcjonowania i wszystkie inne wymagania według normy PN-EN 60849 i innych
odpowiednich norm międzynarodowych i krajowych. Instrukcja taka powinna
zawierać:
• metody konserwacji;
• kolejności odnoszącej się do konserwacji;
• identyfikacji części wymagających konserwacji, przez podanie lokalizacji
poszczególnych elementów na rysunkach razem z fabrycznymi numerami
lokalizacji producenta oraz adresów, numerów telefonów i faksów dostawców
materiałów i części;
• oryginalnej wersji katalogów sprzętu i materiałów;
23
• list i lokalizacji części zapasowych;
• list i lokalizacji narzędzi specjalnych.
Zaleca się również, aby instrukcje konserwacji zawierały:
• certyfikaty badań, które są wymagane podczas kontroli przez odnośne władze;
• komplet dokumentacji powykonawczej.
3. Warunki techniczne instalacji
3.1. Instalacja systemu.
Linie głośnikowe zostaną wykonane certyfikowanymi przez CNBOP przewodami
HDGs PH90 2x2,5mm2 lub HDGs H90 2x4mm2. Na wszystkich poziomach linie
głośnikowe należy instalować stosując uchwyty kablowe stalowe np. Hilti X-FB i XDFB montowane do ściany przy użyciu gwoździ lub kołków ognioodpornych np. typu
DBZ. Poziomy rozstaw uchwytów w odstępach 30cm, rozstaw uchwytów w pionie
może być 1,5 razy większy. Każdy przewód musi być mocowany uchwytem
indywidualnie.
Do układania linii na drabinkach kablowych należy zastosować drabinki/kanały o
klasie odporności ogniowej nie gorszej niż sam kabel. Kanał taki mocować do
podłoża przy pomocy atestowanych kołków metalowych w odstępach 0,5m.
Instalacji wszystkich typów głośników należy dokonywać zgodnie z
instrukcjami instalacji dostarczonymi przez producentów głośników.
Przewód linii głośnikowej należy prowadzić od głośnika do kolejnego głośnika
nie przerywać i nie przedłużać odcinków. Połączenia mogą się odbywać jedynie w
puszce głośnika na kostce ceramicznej. Przewód należy wprowadzać do obudowy
głośnika poprzez dławicę gumową. Nie należy rozgałęziać, ani przedłużać linii
głośnikowej poza obudowę głośnika. Należy zachować tę samą polaryzację
podłączenia głośników do linii.
Poszczególne linie znakować w odległościach pozwalających na ich łatwą
identyfikację dla celów diagnostyczno- remontowych.
Przy przechodzeniu linii głośnikowych przez ściany oddzieleń stref
pożarowych oraz przy przejściach przez stropy należy takie przejścia uszczelnić
ognioochronną pęczniejącą masą uszczelniającą np. CP 611A firmy HILTI.
Za ostatnim głośnikiem na linii należy zamontować moduł końca linii w
obudowie firmy Kabe typ KB-0251, którą należy dodatkowo wyposażyć w kostkę
ceramiczną z bezpiecznikiem termicznym. Obudowę montować przy pomocy kołków
metalowych.
W przypadku dołączenia do systemu mikrofonowych pulpitów wyniesionych
należy zastosować dedykowany kabel umieszczony w rurce niepalnej peschela,
którą należy zamocować przy pomocy stalowych opasek zaciskowych do
dedykowanych kołków wtykanych zamocowanych do ściany lub stropu właściwego,
w przypadku prowadzenia instalacji ponad sufitem podwieszanym.
Kabel zasilający szafę DSO (HDGs 5x6mm2) należy zainstalować w kanale
ochronnym o klasie odporności ogniowej nie gorszej niż sam kabel. Kanał taki
mocować do podłoża przy pomocy atestowanych kołków metalowych w odstępach
0,5m.
24
3.2. Zalecenia instalacyjne:
•
•
•
•
•
Starannie układać przewody, aby nie naruszyć izolacji i nie przekroczyć
minimalnego promienia ich gięcia.
Nie używać nadmiernej siły (większej od katalogowej) podczas przeciągania
przewodów aby nie naruszyć izolacji.
Przed instalacją należy dokładnie zapoznać się z niniejszym projektem.
Zaleca się montaż urządzeń wg DTR producentów z uwzględnieniem
wszystkich uwag zawartych w niniejszym projekcie.
Końcówki przewodów pod zaciski nie wolno zalewać cyną.
3.3. Zalecenia eksploatacyjne.
•
•
•
•
•
Zaleca się, aby każdego roku kompetentna osoba przeprowadzała co najmniej
dwie planowane inspekcje dotyczące konserwacji, której wykonanie powinno
być potwierdzone w dzienniki operacyjnym przez osobę odpowiedzialną za
poprawne działanie i eksploatację systemu.
Akumulatory powinny być użytkowane zgodnie z zaleceniami producenta.
Czas eksploatacji akumulatorów wynosi cztery lata, po upływie tego okresu
należy wymienić akumulatory na nowe.
Konserwacja systemu zgodna z wymogami powinna być powierzona firmie
autoryzowanej przez producenta urządzeń.
Instalacja przewodowa oraz przejścia przez strefy pożarowe wymagają
okresowych przeglądów.
Firma instalująca i/lub konserwująca system DSO powinna uzyskać możliwość
zdalnej diagnostyki oraz oceny uszkodzeń w sytuacjach wymagających
interwencji serwisowej przed podjęciem działań na obiekcie.
3.4. Zalecenia dla Inwestora.
•
•
•
Instalację systemu DSO powierzyć można jedynie profesjonalnej firmie
posiadającej autoryzację producenta aparatury, aby była gwarancja, iż system
będzie zainstalowany, oprogramowany, uruchomiony i zostaną dokonane
wszystkie niezbędne testy zgodnie z podstawowymi dokumentami DTR
producentów – dotyczy również układania kabli.
Przekazanie instalacji użytkownikowi budynku powinno nastąpić protokolarnie
wraz z przekazaniem pełnej dokumentacji systemu DSO, dostępnej dla
organów kontroli. Drugi egzemplarz dokumentacji powinien znajdować się u
uprawnionego konserwatora, z którym Użytkownik zawiera odpowiednią
umowę na konserwację.
W pobliżu szaf DSO należy przechowywać dokumentację w postaci instrukcji
obsługi dla personelu w celu szybkiej reakcji w sytuacjach alarmowych, a w
szczególności identyfikacji zagrożonej strefy i błyskawicznej pomocy w
ewakuacji ludziom.
3.5. Uwagi dla innych branż.
•
•
•
W przypadku nadmiernego grzania się urządzeń w szafach DSO należy
zainstalować w pobliżu szaf urządzenie klimatyzacyjne.
Unikać bezpośredniego dotykania żył przewodów linii głośnikowych (linia
pracuje na napięciu znamionowym 100V).
Unikać prowadzenia przewodów teletechnicznych pracujących na niskich
25
•
poziomach sygnałów w bezpośredniej styczności z liniami głośnikowymi.
W przypadku remontu pomieszczenia należy przed demontażem głośników
zgłosić ten fakt osobie odpowiedzialnej za system oraz firmie konserwującej
system DSO. Nieautoryzowana ingerencja w instalację potraktowana zostanie
przez system jako sabotaż.
3.5.1. Instalacja elektryczna
Niniejszy projekt uwzględnia doprowadzenie 3-fazowego zasilania 400V do systemu
DSO. Projektuje się doprowadzenie zasilania z wydzielonego, oznaczonego pola
rozdzielni głównej. Obwód zasilania należy zabezpieczyć nadprądowo
bezpiecznikiem o wartości podanej przez producenta systemu zasilania DSO.
Ponadto do szafy urządzeń DSO należy doprowadzić uziemienie. Ilość zabezpieczeń
pomiędzy centralą a przyłączem nie może przekroczyć dwóch. W pomieszczeniu
serwerowni (miejscu usytuowania centrali DSO) zapewnić oświetlenie awaryjne.
3.5.2. Integracja systemów
Zgodnie z projektem pierwotnym należy wykonać dwustronną integrację systemów –
DSO i SAP. Centrala SAP wysyła do DSO sygnał alarmu pożarowego II stopnia
wyzwalający komunikat alarmowy. Z kolei centrala DSO wysyła do centrali SAP
sygnał o ewentualnym uszkodzeniu systemu DSO.
Pomiędzy centralami DSO zainstalowanymi na obiekcie MTM należy wykonać
integracja centrali CDSO-1 z centralą nadrzędną CDSO zgodnie z opisem w punkcie
2.7 niniejszego opracowania.
3.6. Uwagi ogólne
ƒ wszelkie zamontowane urządzenia powinny posiadać znak CE;
ƒ wszelkie prace na obiekcie prowadzić z przestrzeganiem obowiązujących
norm i przepisów a w szczególności wymienionych w punkcie 2 niniejszego
projektu;
ƒ system wykonać w oparciu o projekt wykonawczy, z uwzględnieniem
uzgodnień z inwestorem;
ƒ wykonać pomiary:
o ciągłości linii głośnikowych,
o rezystancji linii głośnikowych
o stanu izolacji linii głośnikowych
o zrozumiałości mowy RASTI
o ciśnienia akustycznego [ dB(A)] .
ƒ układane przewody należy oznakować trwałymi oznacznikami z informacją o
typie kabli, posiadanym certyfikacie CNBOP oraz producencie;
ƒ wszystkie urządzenia systemu zainstalować wg DTR producentów z
uwzględnieniem wszystkich uwag zawartych w niniejszym projekcie oraz w
specyfikacji technicznej wykonania i odbioru niniejszej instalacji.
ƒ po wykonaniu i uruchomieniu systemu należy wykonać dokumentację
powykonawczą zawierającą zgodne z rzeczywistością rysunki tras przebiegów
kabli oraz miejsca montażu poszczególnych elementów instalacji;
ƒ końcówki przewodów pod zaciski zakańczać zaciskanymi tulejkami.
26
4. Zalecenia dla użytkownika instalacji
4.1
Zalecenia ogólne
Montaż instalacji może być wykonany tylko przez uprawnionego instalatora
(posiadającego odpowiednie świadectwo producenta/dostawcy systemu).
W czasie odbioru Wykonawca systemu DSO przekaże protokolarnie Inwestorowi
instalację wraz z pełną dokumentacją systemu DSO dostępną dla organów kontroli.
Drugi egzemplarz dokumentacji powinien znajdować się u uprawnionego
konserwatora, z którym Użytkownik zawiera odpowiednią umowę na konserwację.
W szczególności Wykonawca powinien przedłożyć:
ƒ dokumentację powykonawczą, w której naniesiono wszelkie zmiany w
stosunku do projektu wykonawczego, zmiany uzgodnione z projektantem,
ƒ protokoły pomiarów ciągłości instalacji, stanów izolacji oraz rezystancji linii
oraz protokoły z pomiarów uziemień
ƒ ważne certyfikaty na wszystkie elementy systemu (w tym kable)
ƒ wszelkie niezbędne wymagane inne protokoły prób, testów i pomiarów.
W pomieszczeniu, w którym znajduje się centrala DSO należy umieścić:
ƒ Instrukcję Obsługi dla personelu, w celu szybkiej reakcji w sytuacjach
alarmowych, a w szczególności identyfikacji zagrożonej strefy i błyskawicznej
pomocy w ewakuacji ludziom;
ƒ plan sytuacyjny powiadamianych obszarów;
ƒ instrukcję obsługi systemu DSO;
ƒ książkę obsługi technicznej systemu DSO, do której należy wpisywać:
o okresowe kontrole instalacji i urządzeń,
o dokonane naprawy,
o zmiany i uzupełnienia instalacji,
o wszystkie alarmy z podaniem daty i godziny ich wystąpienia,
o wyłączenia głośników, stref, linii itp.
ƒ instrukcję postępowania w przypadku alarmów pożarowych oraz
uszkodzeniowych.
4.2
Szkolenie personelu obsługi
Personel odpowiedzialny za obsługę, kontrolę oraz nadzór nad systemem powinien
być przeszkolony w zakresie wykonywania odpowiednich czynności związanych z
pracą systemu DSO, a w szczególności ze sposobem reagowania na sygnały z
systemu. Fakt przeprowadzenia i odbycie szkolenia powinien być potwierdzony
podpisami osób biorących udział w szkoleniu i prowadzącego na protokole szkolenia.
4.3 Konserwacja systemu DSO
W celu zapewnienia poprawnej pracy systemu DSO winien on podlegać stałemu
nadzorowi konserwatorskiemu. W trakcie prac konserwacyjnych wykonać należy
następujące czynności:
Tabela 5.
L.p. Wyszczególnienie
Przegląd
27
Kwartalny Półroczny
♠
♠
Roczny
♠
1
Sprawdzenie baterii akumulatorów
2.
Test centrali systemu
♠
♠
3.
Sprawdzenie
komunikacji
z
urządzeniami peryferyjnymi
Sprawdzenie
zadziałania
zainstalowanych głośników
♠
♠
♠
♠
4.
W pomieszczeniu centrali systemu DSO powinny się znajdować:
- dokumentacja techniczna budowlana powykonawcza oraz
- Dziennik Konserwacji i Obsługi Awaryjnej Systemu, w którym należy dokonywać
wpisów odnośnie wszelkich czynności serwisowych.
Wpisy powinny być potwierdzone podpisem serwisanta i przedstawiciela
Użytkownika systemu.
5. Zestawienie materiałów
Lp. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. Nazwa Ceramiczna kostka z bezpiecznikiem termicznym Dławnica kablowa BDe 13,5 + nakrętka farba olejna nawierzchniowa szara Głośnik kolumnowy LBC 3210, 60W Głośnik naścienny WAC 165/6 PP1 Głośnik naścienny WAC 165/6 PP1, 6W, wyk. łazienkowe Głośnik projektorowy DAW 130/20 PP Głośnik sufitowy DELF 165/6 PP 6W wraz z osłoną Głośnik tubowy LBC 3482/00, 25W gniazdo podtynkowe w kasecie naściennej z zamkiem , IP65 haczyki stalowe Impedancyjny moduł kontroli 2 linii głośnikowych, ABT‐
V200IMK2 Interfejs między SAP i DSO, ABT‐V200SAP Jednostka kontroli,ABT‐V2000JK Jednostka zarządzająca systemem zasilania, ABT‐V2000JZ KCOP N 100H60/3N E‐30 ‐ Komplet zawiesi do koryta typu KCOP KCOP N 100H60/3N E‐30 ‐ korytka kołki rozporowe plastikowe fi+6 Kołki rozporowe stalowe Kołki rozporowe stalowe kołki wstrzeliwane z nabojem i osłoną konstrukcja stalowa z kotwami i śrubami o masie 3 kg konstrukcje wsporcze koryto kablowe (kpl.) 100H50 28
Jm opak. szt. dm3 szt szt szt kpl szt szt kpl. szt. Ilość 1 740 2,16 93 156 4 52 47 18 9 506 szt szt szt szt 24 1 3 3 szt m szt. szt szt szt. kpl. szt. m 744 252,96 270 9 547,00 506 297 18 300 330 25. Linka certyfikowana do zwieszania głośników DSO Materiały instalacyjne (stalowa linka, ucho metalowe, 26. podkładka, nakrętka, kotwa metalowa) 27. Menadżer systemu ABT‐V2000 28. Mikrofon strażaka,, ABT‐V200MS 29. Mikrofon strefowy, ABT‐V200M 30. Moduł wejściowy mikrofonu, ABT‐V200MWM 31. Moduł wejściowy wzmacniacza mocy, ABT‐V200MWW 32. Moduł wejściowy wzmacniacza mocy+ BGM, VP‐200VX‐BGM 33. Obudowa typu KABE, KB0251 34. Ognioochronna masa uszczelniająca CP 611A 35. opaski plastikowe Płyta zapowiedzi głosowych + karta pamięci, ABT‐V200PZG + 36. EVCE128Q 37. Programowanie i uruchomienie systemu Venas 38. przewody kabelkowe HTKSH4x2x1,4mm, PH90 39. przewody kabelkowe HTKSHekw 2x2x0,8mm 40. przewody kabelkowe STP 4x2x0,5mm kat.5e 41. Przewód HDGs 2x2,5mm2 PH90 42. Przewód HDGs 2x4mm2 H90 43. Przewód HDGs 5x6mm2 H90 44. Rama zasilaczy, ABT‐V2000RZ 45. Rozszerzenie mikrofonu, ABT‐V210RM 46. Rozszerzony Mikrofon strażaka, ABT‐V200RMS 47. Skrzynka wyniesionego mikrofonu strażaka, ABT‐SMS 48. Spoiwo cynowo‐ołowiowe z kal.5A LC 60 3mm 49. Szafa systemu DSO, okablowana, z 2 akumulatorami 120 Ah 50. Szafa systemu DSO, okablowana, z 2 akumulatorami 160 Ah 51. Ścienny uchwyt pulpitów mikrofonowych Śruby stalowe średnodokładne z gwintem na całej długości 52. M‐6 53. śruby z akcesoriami 54. uchwyt kabla typu UDF E90 55. uchwyty 56. Uchwyty stalowe, certyfikowane 57. Wtyki (łącza przy aparaturze elektroakustycznej) 58. Wzmacniacz mocy 240W 100V, ABT‐V2241WM 59. Wzmacniacz mocy 2x120W 100V, ABT‐V2122WM 60. Zasilacz, ABT‐V200Z 61. złącze RJ45 STP kat.5e 62. Materiały pomocnicze 29
m 1 760,00 kpl. SZT szt szt szt szt szt szt szt szt 47 1 2 7 8 23 4 24 8 6 180,00 szt kpl. m m m m m m szt szt szt kpl kg kpl kpl szt 2 1 312 312 2 142,40 3 478,40 5 052,00 104 3 4 1 3 0,11 2 1 4 kg szt. szt. szt. szt szt. szt szt szt szt. zł 48 612 270 270 9 180,00 24 10 9 9 22 6. Przedmiary robót.
Lp. Podstawa jedn.obm. Obmiar Mechaniczne przebijanie otworów w ścianach lub stropach betonowych o długości przebicia do 20 cm ‐ śr. rury do 25 mm otw. 120 Mechaniczne przebijanie otworów w KNR 4‐03 1004‐ ścianach lub stropach betonowych o 11 z.o.3.1. 9901‐ długości przebicia do 30 cm ‐ śr. rury do 25 mm ‐ budowle o wys.do 24 m 2 d.1 6 otw. 40 szt. m 160 <KCOP N 100H60/3N E‐30 >744 = 744,00 <KCOP N 100H60/3N E‐30 >744 = 744,00 m <Przewody HDGs 5x6mm2>100 = 100,00 KNR 5‐08 0211‐
02 z.o. 3.1. 7 d.1 9901 Przewody kabelkowe n.t. w powłocepolwinitowej (łączny przekrój żył do 12‐Cu/20‐Almm2) mocowane paskami lub klamerkami na przygotowanym podłożu Instalacje w halach powyżej 4 do 12 m. m <Przewody HDGs 5x6mm2 H90>100 = 100,00 KNR 5‐08 0201‐
8 d.1 02 Montaż uchwytów pod przewody kabelkowe układane pojedynczo z przyg.podłoża mechanicznie ‐ przykręcanie do kołków stalowych w podłożu z cegły m 2700 KNR 5‐08 0211‐
9 d.1 06 Przewody kabelkowe (łączny przekrój żył do 6‐Cu/12‐Al mm2) mocowane na uprzednio zainstalowanych uchwytach odstępowych m 2700 Przewody kabelkowe o łącznym przekroju żył do 7.5 mm2 układane w gotowych korytkach i na drabinkach na KNNR 5 0209‐04 uchwytach bezśrubowych m 4000 1 KNR 4‐03 1004‐
1 d.1 06 Opis Dźwiękowy system ostrzegawczy ‐ wybudowanie tras kablowych i ułożenie okablowania Uszczelnianie częściowo zajętych lub wolnych otworów wprowadzeń KNR 5‐01 0606‐ kablowych do rury ogniochronną masą uszczelniającą, poz zastępcza 3 d.1 09 Konstrukcje wsporcze przykręcane o 4 d.1 KNNR 5 1101‐01 masie do 1 kg ‐ 1 mocowanie Korytka o szerokości do 200 mm 5 d.1 KNNR 5 1105‐08 przykręcane do gotowych otworów Montaż uchwytów pod przewody kabelkowe układane pojedynczo z przyg.podłoża mechanicznie ‐ KNR 5‐08 0201‐ przykręcanie do kołków wstrzeliwanych Instalacje w halach powyżej 12 do 24 04 z.o. 3.1. m. 6 d.1 9901 10 d.1 30
m 11 d.1 12 d.1 Konstrukcje wsporcze przykręcane o masie do 2 kg ‐ 2 mocowania ‐ analogia KNNR 5 1101‐04 dla przewodów zwieszanych KNR‐W 5‐08 0215‐01 z.o. 9901‐6 szt. 1760 Przewody kabelkowe o łącznym przekroju żył do 7.5 mm2 układane na gotowych linkach nośnych z mocowaniem zapinkami z taśmy lub drutu ‐ roboty w budowli o wysokości 12‐24 m m 460 Przewody kabelkowe o łącznym przekroju żył do 12.5 mm2 układane na gotowych linkach nośnych z mocowaniem zapinkami z taśmy lub drutu ‐ roboty w budowli o wysokości 12‐24 m Integracja z systemem DSO Etap I. m 1300 13 d.1 KNR‐W 5‐08 0215‐02 z.o. 9901‐6 2 45312100‐8 14 d.2 KNR AT‐13 0108‐03 Konstrukcje wsporcze pod drabinki i koryta kablowe o masie do 1 kg montowane na ścianie szt. 300 15 d.2 KNR AT‐13 0109‐04 Koryta kablowe (odcinki proste) o szer. do 100 mm ‐ integracja a z systemem DSO Etap I m 300 KNR‐W 5‐08 0211‐01 z.o. 9901‐6 Przewody kabelkowe n.t. o łącznym przekroju żył do 7.5 mm2 mocowane paskami lub klamerkami na przygotowanym podłożu ‐ roboty w budowli o wysokości 12‐24 m m <HTKSHekw 2x2x0,8mm ; do DSO Etap I >300 = 300,00
KNR‐W 5‐08 0211‐01 z.o. 9901‐6 Przewody kabelkowe n.t. o łącznym przekroju żył do 7.5 mm2 mocowane paskami lub klamerkami na przygotowanym podłożu ‐ roboty w budowli o wysokości 12‐24 m m <HTKSH 4x2x1,4mm : Mikrofon strażaka rozrzerzony do szafy DSO Etap I >300 = 300,00 16 d.2 17 d.2 3 45312100‐8 18 KNR AT‐15 d.3 0108‐02 19 KNR AT‐14 d.3 0105‐02 20 d.3 KNR‐W 5‐08 0211‐01 z.o. 9901‐6 Podłączenie mikrofonów wyniesionych Montaż gniazd abonenckich podtynkowych Montaż złącza RJ45 na skrętce 4‐
parowej ekranowanej STP/FTP szt. 9 szt. 11*2 = 22,00 Przewody kabelkowe n.t. o łącznym przekroju żył do 7.5 mm2 mocowane paskami lub klamerkami na przygotowanym podłożu ‐ roboty w budowli o wysokości 12‐24 m m 2060 31
23 d.4 KNR 5‐08 0403‐
01 Montaż uchwytów pod przewody kabelkowe układane pojedynczo z przygotowaniem podłoża mechanicznie ‐ przykręcanie do kołków plastikowych w podłożu betonowym ‐ roboty w budowli o wysokości 12‐24 m Wykonanie pomiarów torów transmisyjnych zgodnie z wymaganiami Montaż głośników DSO Mocowanie na gotowym podłożu aparatów o masie do 2.5 kg z częściowym rozebraniem i złożeniem bez podłączenia (il. otworów mocujących do 2) ‐ metalowa obudowa głośnika panelowego, bez ceny urządzenia 24 d.4 KNR 5‐06 0803‐
09 Instalowanie głośnika wnętrzowego o mocy 10 W w obudowie zwykłej na ścianie betonowej KNR 5‐06 0810‐
02 Instalowanie głośników zewnętrznych jednokierunkowych na gotowych konstrukcjach wsporczych na ścianie betonowej szt. <Głośnik tubowy LBC 3482/00, 25W>18 = 18,00 KNR 5‐06 0806‐
02 Instalowanie głośnika wnętrzowego o mocy 10 W w obudowie szczelnej na suficie podwieszanym szt. <DEF 165/6 PP, 6W>47 = 47,00 szt. <Głośniki projektorowe DAW 130/20 PP>52 = 52,00 szt 370*2 = 740,00 szt. 24 szt. 24 szt. 24 szt. 3 szt. 9 szt. 10 elem. 19 KNR‐W 5‐08 0201‐03 z.o. 21 d.3 9901‐6 22 KNR AT‐14 d.3 0111‐01 4 45312100‐8 25 d.4 26 d.4 Instalowanie głośnika wnętrzowego o mocy 20 W w obudowie szczelnej na 27 KNR 5‐06 0806‐ suficie metalowym ‐ analogia dla montażu na linkach zwisowych d.4 03 28 Montaż przepustów kablowych w d.4 analiza własna obudowie głośnika 29 KNR 5‐06 0801‐ Instalowanie zestawu do nadzoru linii d.4 03 głośnikowych (poz. zast.), 30 KNR 5‐06 0801‐ Instalowanie obudowy modułów końca d.4 03 linii KABE KB‐0251 ‐ (poz. zast.), 31 KNR 5‐01 0817‐ Montaż kostki ceramicznej do obudowy d.4 02 Kabe , (poz. zast.) 5 Aparatura elektroakustyczna DSO 32 KNR AL‐01 0102‐ Montaż modułowej centrali alarmowej d.5 03 do 32 linii dozorowych 33 KNR AL‐01 0112‐ Montaż zasilacza do 12 V DC/240 W ‐ d.5 08 analogia 34 d.5 35 d.5 KNR 5‐06 0304‐
05 KNR 5‐06 0205‐
04 Instalowanie skrzynek mikrofonowych z sygnalizacją z dwoma gniazdami na stole ‐ poz. zast. Instalowanie wzmacniaczy liniowych w stojakach 32
m 100 pomiar 11 szt. 160 szt. 253 36 d.5 37 d.5 KNR AL‐010106‐
01 KNR 5‐06 0708‐
01 6 45312100‐8 38 d.6 KNR 5‐02 1503‐
01 39 d.6 40 d.6 41 d.6 42 d.6 KNR‐W 5‐08 0902‐01 ANALIZA WŁASNA kalkulacja własna Kalkulacja własna 43 d.6 44 d.6 45 d.6 46 d.6 KNR‐W 5‐08 0902‐0300 KNR‐W 5‐08 0901‐0100 KNR 4‐03 1203‐
03 KNR 5‐06 0501‐
01 7 47 d.7 48 d.7 49 d.7 AL 1 0703‐02 KALWL 1 0201‐
01 KALWL 1 0101‐
01 Instalowanie na stojaku Modułów cyfrowych centrali SAP _ insatalacja interfejsów ‐ poz. zast. Montaż wtyków przy aparaturze elektroakustycznej Pomiary i uruchomienie systemu DSO urządzenie 1 szt. 24 odc. 370 pomiar 370 kpl. 1 Sprawdzenie i uruchomienie głośników szt 370 Pomiary wsp. zrozumiałości mowy szt. 370 pomiar 1 pomiar 3 odc. 3 zesp. 3 kpl 1 kpl 1 kpl 1 Pomiar rezystancji izolacji żył w kablach z parami symetrycznymi ‐ do 10 par Krotność = 0,1 Sprawdzenie samoczynnego wyłączenia zasilania ‐ pomiar impedancji pętli zwarciowej ‐ pierwszy ‐ analogia dla pomiaru impedancji pętli linii głośnikowej Programowanie i uruchomienie systemu VEVAS Sprawdzenie samoczynnego wyłączenia zasilania ‐ pomiar rezystancji uziemienia ‐ pierwszy Pomiar rezystancji izolacji instalacji elektrycznych ‐ obwód 1‐fazowy, pierwszy pomiar Badanie linii kablowej sterowniczej o ilości żył do 20 Krotność = 0,4 Uruchomienie zespołów realizacji programów o 10 liniach wej./wyj. Dokumentacja powykonawcza i szkolenie Wykonanie dokumentacji powkonawczej Opracowanie instrukcji obsługi systemu
Szkolenie personelu w zakresie obsługi systemu DSO 33
8.
Oświadczenia i uprawnienia projektanta i sprawdzającego.
34
7. Zestawienie rysunków
Rys. 1: Schemat blokowy Dźwiękowego Systemu Ostrzegawczego
DSO.
Rys. 2: Instalacja systemu DSO– rzut łącznika hali – poziom -500.
Rys. 3: Instalacja systemu DSO– rzut hali poziom +0,00.
Rys. 4: Instalacja systemu DSO– rzut hali poziom +350.
Rys. 5: Instalacja systemu DSO– rzut hali poziom +910.
9.
Certyfikaty i dane techniczne – karty urządzeń i elementów.
35
Niniejsza dokumentacja zawiera wszelkie niezbędne Certyfikaty, deklaracje
zgodności i karty katalogowe projektowanego systemu DSO.