service case automatic power switch tester

Transkrypt

service case automatic power switch tester
SERVICE CASE
AUTOMATIC POWER SWITCH TESTER
TECHNICAL AND
OPERATIONAL DOCUMENTATION
1. APPLICATION
The type W-27 was designed for special demand of groups occupied with startup of electric power
stations. The main purpose of the case is testing SZR (automatic power switch) type of devices. It
can also be used to simulate the state of connectors, switch, grounding and reaction of the system
to planned events.
2. CONSTRUCTION
The device is powered from a 230V AC grid. The service case is equipped with 2 independent, wire
fuse secured, transformers of direct current for provision of power supply and controls to the
110VDC and 220VDC devices. The case allows the connection of a 3-phase 3x400V current, and –
with use of toroidal transformer – transforms the voltage to a 3x100V level that can be used for
measurement circuits of the tested device. The faceplate features three wire fuses, used to secure
the voltage/measurement circuits from short circuits or overcurrent. All banana jack connectors
built on the front of the device are secure laboratory sockets. The device has 8 indicator LEDs that
are activated through potentials on the respective optical connectors paired with them.
Napięcie
Linii 1wyjście
L1
ZAŁ
ZAŁ
WYŁ
WYŁ
Napięcie
Linii 2wyjście
L2
Wyjścia
Wyjścia
Wejścia
Wejścia
Załaczony
L3
Załaczony
ZAŁĄCZ
TRYB
N
PRA CY
PRACY
WYŁĄCZ
WYŁĄCZ
Wyłączony
Wyłączony
Gotowy
PE
3x400V
ZAŁĄCZ
TRYB
Gotowy
WALIZKA SERWISOWA
TYP W-27
TESTER SZR-15kV
3x100V
Wejścia napięć do pomiaru
Wyjścia
Wejścia
Załaczony
FUSE
Wyjścia
Wejścia
Załaczony
ZAŁĄCZ
TRYB
ZAŁĄCZ
TRYB
PRA CY
PRACY
WYŁĄCZ
WYŁĄCZ
Wyłączony
Wyjście 110 VDC
Imax=100mA
Wejścia sygnalizacyjne
Wyłączony
Gotowy
Gotowy
FUSE
L1
L2
L3
FUSE
FUSE
FUSE
N
L1
L2
L3
ZAŁ
ZAŁ
ZAŁ
ZAŁ
ZAŁ
ZAŁ
WYŁ
WYŁ
WYŁ
WYŁ
WYŁ
WYŁ
L1
ZAŁĄCZ
TRYB
Wejście napięcia
sterowniczego
Zabezpieczenie obwodów
napięciowych Imax=150mA
Zasilanie testera
L3
Wyjścia
3x100V
RS232
N
WYŁĄCZ
PRA CY
Wyjście 220 VDC
Imax=100mA
L2
3x100V
Zał.
Wyjście napięcia - Sekcja 1
Wył.
Gotowy
Wyjście napięcia - Sekcja 2
Wyjścia pomocnicze - blokady
ZAŁ
ZAŁ
ZAŁ
ZAŁ
ZAŁ
ZAŁ
ZAŁ
WYŁ
WYŁ
WYŁ
WYŁ
WYŁ
WYŁ
WYŁ
Fig. 1. Faceplate of the W-27 service case
3. STARTUP
The voltage should only be connected with use of the special computer cord, as provided together
DTR W-27_06.2014
2
with the case.
WARNING: the device is used for work in NT-S type of power grid with efficient grounding. Failure to
meet that condition may lead to the appearance, on metal surfaces of the device cover, of
dangerous electric potentials that pose substantial threat to both the service personnel and the
device itself.
After switching on the power supply connect the appropriate banana jack sockets should be
connected in order to select the steering voltage. The sockets marked “steering voltage input”
should be powered with 110 or 220V DC from the transformer of the case or an external source of
voltage. In no event should the voltages of 110 and 220V be connected together, or an outer source
connected with the power from the case transformer – this will cause significant damage to the
device. In order to facilitate the power supply of the tested devices three transformers lowering the
3x400V voltages of the interphase voltage. Thus 3x230V or 3x100V should be directly connected. It
is forbidden to connect both of those voltages simultaneously.
After the aforesaid preparation of case for work the tested inputs and outputs of the tested device
can be connected. In order to prevent connection errors, that could potentially damage the case,
the optical input connectors of the case were made in form of white banana jack sockets, and the
output connectors are made as violet banana jack sockets.
4. USE
The device is dedicated for testing medium voltage SZR automatic. Thanks to its universal character
it allows the connection of every manufacturer’s SZR devices. The device allows the connection of 5
switches, that is their copies (on/off/standby) and the on/off controls of the switches. The auxiliary
connectors placed on the elevation of the device can simulate different types of signals and feed
them to the tested device. As a standard – the tester switches are armed after switching off of the
switch, but there is the possibility of reversing the logic of readiness by pressing a set combination
of keys. Arming “on on” is switched by pressing buttons 1 and 10 for approx. 5 seconds, arming “on
off” by pressing buttons 2 and 9. This means that if there is voltage present on the line and the
switches are shut. You can switch off this function by pressing down buttons 4 and 7 for
approximately 5 seconds. After reloading supply the situation will revert to as state in which the
presence of voltage depends again on the state of the switches.
DTR W-27_04.2014
3
Napięcie
Linii 1wyjście
L1
ZAŁ
ZAŁ
WYŁ
WYŁ
L2
1
Wyjścia
Wejścia
Załaczony
L3
N
Załaczony
ZAŁĄCZ
TRYB
ZAŁĄCZ
TRYB
PRACY
PRACY
WYŁĄCZ
WYŁĄCZ
Wyłączony
Wyłączony
Gotowy
PE
3x400V
Wyjścia
10
Wejścia
Gotowy
2
3x100V
Wejścia napięć do pomiaru
Wyjścia
9
WALIZKA SERWISOWA
TYP W-27
TESTER SZR-15kV
3
Wejścia
Załaczony
8
Wyjścia
Wejścia
Załaczony
ZAŁĄCZ
TRYB
ZAŁĄCZ
TRYB
PRACY
PRACY
WYŁĄCZ
WYŁĄCZ
Wyłączony
Wyjście 110 VDC
Imax=100mA
Wejścia sygnalizacyjne
Wyłączony
Gotowy
Gotowy
7
4
L1
L3
L2
N
L1
L2
L3
ZAŁĄCZ
TRYB
ZAŁ
Zabezpieczenie obwodów
napięciowych Imax=150mA
Zasilanie testera
RS232
WYŁ
WYŁ
5
6
Zał.
Wyjście napięcia - Sekcja 1
L2
L3
ZAŁ
ZAŁ
ZAŁ
WYŁ
WYŁ
WYŁ
N
Wyjścia
ZAŁ
3x100V
WYŁ
Wejście napięcia
sterowniczego
ZAŁ
L1
WYŁĄCZ
PRACY
Wyjście 220 VDC
Imax=100mA
Napięcie
Linii 2wyjście
Wył.
Gotowy
3x100V
Wyjście napięcia - Sekcja 2
Wyjścia pomocnicze - blokady
ZAŁ
ZAŁ
ZAŁ
ZAŁ
ZAŁ
ZAŁ
ZAŁ
WYŁ
WYŁ
WYŁ
WYŁ
WYŁ
WYŁ
WYŁ
Fig. 2. Button numbers for setup changes.
WARNING!
All work conducted with the use of W-27 case shall be conducted pursuant to safe work
practice guidelines for Low Voltage operating devices.
DTR W-27_04.2014
4
General data
Insulatio
n
Voltage
connectors
Supply
voltage
5. TECHNICAL DETAILS
Supply voltage UN
230V AC
Permissible voltage range
0.9xUN to 1.1xUN
Power consumption
< 50W
100 V AC +/-5% - voltage
circuits
Outputs
220V DC – control circuits
Rated voltage
400V AC L-L
Electric strength
2.5kV; 50 Hz; 1 min.
Case protection grade
IP-40
External dimensions
524/428/206
Ambient humidity
<95%
Operating temperature range
From -5oC to 40oC
Mass in service
12 kg
Tab.1. Technical details
6.
CE MARKING
The CE marking was performed in 2014 The marking is placed on the rating plate on the lid of the
case. The rating plate is shown on figure 2. The rating plate includes the basic parameters of the W27 service case.
Nazwa
Typ wyrobu
Walizka serwisowa
typ W-27
Nr 0001 Rok produkcji 04.2014
Wymiar S/W/G 524/428/206
Uz
12
0,5A Masa /kg/
Iz
I
IP
40 Klasa ochronności
Norma odniesienia PN-EN 61810-1:2008
Fig. 2. Rating plate of the W-27 service case
DTR W-27_04.2014
5
7.
SERVICE
The devices manufactured by Energoaparatura SA are subject to standard, two-year warranty
period.
The warranty and post-warranty services are provided in the premises of the Energoaparatura SA
company in Katowice.
8. PROCEDURE FOR WASTE MANAGEMENT OF USED ELECTRONIC DEVICES.
Pursuant to the 29 July, 2005 used electric and electronic devices Act (Journal of Laws “Dz.U.” No.
180, item 1495) the used product shall be returned to the Energoaparatura SA company or to a
company providing utilization services for electronic waste.
9. FURTHER CUSTOMER INFORMATION
In technical matters :
In sales-related matters:
Jacek Gumul
Head of Electronics Department
tel. +48 32 728 55 73
[email protected]
Marta Szpaczyńska
Marketing Specialist
tel. +48 32 728 54 05
[email protected]
DTR W-27_04.2014
6