Installation instructions

Transkrypt

Installation instructions
Mounting instructions
Polyester –ATEX / IECEx enclosures
Explosion proof junction boxes
PEM804/Rev A, 15.7.2014
Empty Boxes:
Junction Box:
II 2G Ex e IIC Gb
II 2G Ex e IIC T6/T5 Gb
II 2D Ex tb IIIC Db II 2G Ex ia IIC T6/T5 Gb
II 2D Ex tb IIIC T85°C/T100°C Db
Programme Overview
MGRPEX Ex e / Ex tb / Ex ia
Ensto code
MGRPEX080806
MGRPEX080808
MGRPEX081106
MGRPEX081108
MGRPEX081606
MGRPEX081608
MGRPEX081906
MGRPEX081908
MGRPEX082305
MGRPEX082308
MGRPEX121209
MGRPEX122209
MGRPEX161609
MGRPEX162609
MGRPEX163609
MGRPEX165609
MGRPEX252512
MGRPEX254012
MGRPEX256012
MGRPEX404012
MGRPEX252516
MGRPEX254016
Ensto
articlenumber
3211100150E
3211100250E
3211100370E
3211100450E
3211100550E
3211100650E
3211100750E
3211100850E
3211100950E
3211101050E
3211101150E
3211101350E
3211101250E
3211101450E
3211101550E
3211101950E
3211101660E
3211101760E
3211102050E
3211101850E
3211101670E
3211101770E
Short code
807555P
807575P
117555P
117575P
167555P
167575P
197555P
197575P
237550P
237575P
121290P
221290P
161690P
261690P
361690P
561690P
252512P
402512P
602512P
404012P
252516P
402516P
Content
1. Safety Notes
2. Conformity to Standards
3. Technical Data
4. Commissioning Terminals
5. Assembly Options
6. Earthing/Protective Ground Connection
7. Cable and Wire Installation, Sealing Plugs
8. Installation
9. Maintenance
10. Not Fully Assembled Ex-Junction Boxes
Mounting instruction for polyester –ATEX / IECEx enclosures
Explosion proof junction boxes
1. Safety Notes
3. Technical Data
Target group: Experienced, ex-trained
electricians
These junction boxes are not suitable for the
zones 0 and 20. The temperature classification
and explosives group, marked on the junction
boxes, must be complied with. The user must
observe the requirements of EN 60079-0:2012,
EN 60079-7:2007, EN 60079-11:2012, EN 6007931:2009, IEC 60079-0:2011, IEC 60079-7:2006,
IEC 60079-11:2011 and IEC 60079-31:2013 regarding excessive dust settlements and temperatures. Conversions or alterations to the
junction box are not permitted. One exception
is the fixing of additional cable and wire installations and the mounting of terminals as part of
certification of the equipment, see chapters 6,
8, and 11. They must be operated in accordance
with regulations, undamaged and in perfect
condition. Only original Ensto spare parts must
be used for replacement and repair. Repairs,
which involve the explosion protection, must
be carried out only by Ensto or qualified electricians, in accordance with nationally valid regulations. All foreign objects (transport stoppers
for example) without an appropriate Ex-certificate must be removed from the junction boxes
before first use. Appropriate safety procedures
must be applied according to electrostatic
regulations (see chapter 7 Earthing / Protective
Ground Connection). Incorrect or unauthorised
operation as well as non-compliance with the
instructions of this operating manual invalidates the warranty.
Observe the national safety and health
regulations and the following safety instructions in the operating manual.
Manufacturer: Ensto Finland Oy
2. Conformity to Standards
This equipment is tested for use in explosive
areas and certified according to:
• Regulation 94/9/EC
• EN 60079-0:2012, EN 60079-7:2007,
EN 60079-11:2012 and EN 60079-31:2009
• IEC 60079-0:2011, IEC 60079-7:2006,
IEC 60079-11:2011 and IEC 60079-31:2013
When installing and operating explosion-proof
electrical equipment, the national regulations
and the statutory order for electrical installations in explosive areas must be observed. The
junction boxes are certified for use in explosive
areas of zones 1, 2, 21 and 22.
For the enclosures MGRPEX080806 to
MGRPEX082308 the Impact test was executed
according to 26.4.3 of EN 60079-0 with a lower
impact force. The installation has to be effected in a way, that the enclosures are protected
against mechanical impacts with an impact energy bigger than 4J.
8
2
Explosion Protection:
Empty Boxes:
• II 2G Ex e IIC Gb
• II 2D Ex tb IIIC Db
Junction Box:
•
II 2G Ex e IIC T6/T5 Gb
•
II 2G Ex ia IIC T6/T5 Gb
•
II 2D Ex tb IIIC T85°C/T100°C Db
Certificates:
IBExU 14 ATEX 1126U
IBExU 14 ATEX 1128X
IECEx IBE14.0042U
IECEx IBE14.0043X
Box material: Polyester
Rated voltage:
max. 1100 V (depending on components)
Rated current: max. 452 A
Max. conductor diameter:
max. 300 mm2 (depending on components)
Protective conductor diameter:
max. 150 mm2 (depending on components)
Degree of protection:
IP66 according to EN/IEC 60529
Service temperature: according to each
installation, for polyester: a maximum of -55°C
to + 100°C
Ambient temperature: -20°C to + 40°C (conform to T6 = 85°C) or -55°C to +40°C with special identification and appropriate installation
and attachment parts (conform to T5 = 100 °C).
Identification:
• K 0537 6 II 2 G Ex e IIC Gb, II 2 D Ex tb IIIC Db
• K 0537 6 II 2 G Ex e IIC T6 or T5 Gb,
II 2 G Ex ia IIC T6 or T5 Gb
• K 0537 6 II 2 D Ex tb IIIC T85°C or T100°C Db
4. Commissioning Terminals
Before starting up the following must be
noted:
• Only defined Ex -certified terminals are
allowed, contact Ensto
• Max. cross-section
• Max. current
• Max. voltage
When exchanging or adding terminals, the
same type of terminal must be used. Repair or
overhaul is permitted only with Ensto Finland
Oy approved spare-parts and accessories.
5. Assembly Options
Because of contact resistance at the clamping
points and because of the connectors housed
in the box, heat is produced, which must not
exceed the maximum permissible temperature of the junction box. The electric load to
the power circuit in the junction box must be
adjusted accordingly. The maximum permissible number of connectors for each junction
box, depending on electric load and connector diameter, can be seen in the layout diagram
housed in each box (Example see Table 1).
6. Earthing / Protective Ground
Connection
Ex enclosures must be earthed according to
the specifications of IEC/EN 60079. For electrical earthing it must always be ensured that all
earthing conductor cross-section are appropriately dimensioned according to the actual
cross-section of the supply. Metal flanges, covers, metal plates and metal screw connections
must be included in the potential equalization.
When busbars are used for protective connectors, each clamping bracket may hold 2 conductors up to 6 mm2. If only 1 conductor is connected, it must be bent into a loop, to achieve
consistent contact pressure via the bracket.
7. Cable and Wire Installation,
Sealing Plugs Connection
According to IEC/EN 60079-0 Appendix B, only
Ex- certified cable glands and sealing plugs
must be used. Only permanently fixed cables
and wires must be installed. The operator must
ensure appropriate strain relief.
When used in Ex dust areas, only ex-certified
cable glands and sealing plugs may be used.
Distance to drilling must be observed according to Table 2.
The cable glands and sealing plugs could
become loose during transport, remember to
re-tighten.
You, as the installer, are therefore obliged to
examine the screw connections and sealing
plugs appropriately, according to regulations
and to tighten them, if necessary, when the
equipment is being installed.
8. Installation
The relevant IEC/EN standards and national
regulations of the equipment safety legislation
as well as generally acknowledged technical
PEM804/REV A
© ENSTO 2014
standards are binding for installation and operation. When installing, a conductive or dissipative connection to the earth must be ensured.
Before the enclosure is opened, make sure that
it is de-energized and that appropriate safety
measures are applied.
To maintain the degree of protection and
the protection type use only Ensto assembly
materials.
Caution: Enclosures must be un-damaged
to maintain the tested, technical features.
The operator must handle empty enclosures only according to relevant standards.
Improper installation and operation of the
junction boxes will cause the loss of certification and guarantee.
9. Maintenance
IEC/EN standards and national regulations,
which apply to the maintenance of electrical
equipment in explosive areas, must be observed.
Ensure that the enclosures is de-energized
before opening.
It is permitted to work on intrinsically safe circuits when they are under voltage.
10. Not Fully Assembled ExJunction Boxes
Due to the fact that you, as the customer of Ensto, receive an incomplete piece of equipment,
which is tested and certificated according to
EN 60079-0:2012, EN 60079-7:2007, EN 6007911:2012, EN 60079-31:2009, IEC 60079-0:2011,
IEC 60079-7:2006, IEC 60079-11:2011 and IEC
60079-31:2013, you are obliged to carry out
individual testing according to specified IBEXU
examined manufacturing details when addons take place.
•
•
•
•
•
•
•
•
Max. cross section
Max. voltage
Ex- certified cable glands and sealing plugs
Secure fastening of cable glands and sealing
plugs
Earthing methods/protective ground connection as well as potential equalization according to IEC/EN 60079-0
Air - and creepage distances according to
IEC/EN 60079-7
Ex- certified terminals, whereby assembly
and permanent current must be in accordance to each individual assembly plan.
Connecting components, connections and
connecting clamps from intrinsic safety ignition protection type “i” must comply with
the specifications of EN 60079-11.
As Ensto Finland Oy is responsible for manufacture and individual testing, it is compulsory that the points referring to IEC/EN
60079-0 and IEC/EN 60079-7 are observed,
as the approved Ex- certificate is otherwise
in-valid.
Table 1: Assembly plan for enclosure MGRPEX163609 (example only)
Current
Amp.
6
10
16
20
25
35
50
63
80
100
125
160
200
225
max.
terminals
Terminal-Diameter mm²
1,5
53
18
7
2,5
4
35
20
9
138
40
22
6
6
10
16
25
35
70
95
In this section, fittings may be added to the box as required, provided
that instructions and the specified installation sizes are observed.
43
17
2
42
14
4
35
16
58
6
18
Components in this section require a separate heating veri- 7
fication
65
17
7
69
17
56
50
47
35
24
20
18
Explanations to Table 1:
1. All current-carrying conductors have to be taken into account: protective conductors and
bridges do not count.
2. Non-critical Section (1)
This part of the table is not critical with respect to the box heating up. In this section the maximum amount of terminals may be assembled in the box.
3. Critical Section (2)
This section of the table shows the maximum permissible number of conductors with regard
to their conductor cross-section and the continuous currents, which load the conductors.
Mixed assemblies are possible with power circuits of different cross-section and Example for enclosure MGRPEX163609 Ex-e/tD:
Number
Load
currents; here, the percentage load share of
CrossCurrent
section
(in A)
each individual power circuit must be considered. (See calculation example)
2.5 mm²
16
10 (of 35)
29%
4. Danger Section (3)
16 mm²
50
12 (of 35)
34%
This table section is not permitted with re25 mm²
63
10 (of 58)
17%
gards to heating of the box. Components,
which are referred to in this section, must
Total:
80% < 100%
not be used.
In case of mixed assemblies Ex e/Ex ia, the necessary minimum distances according to EN 60079-11 must be applied.
5. Calculation Example for Mixed Assembly.
Table 2: Drilling Distance for Cable Glands.
M
PG
Distance
M
PG
Distance
M
PG
Distance
12
16
20
20
25
32
40
50
63
63
M
7
9
11
13.5
16
21
29
36
42
48
PG
20 mm
22 mm
26 mm
27 mm
32 mm
42 mm
53 mm
63 mm
70 mm
75 mm
Distance
12+16
12+20
12+20
12+25
12+32
12+40
12+50
12+63
12+63
7+9
7+11
7+13.5
7+16
7+21
7+29
7+36
7+42
7+48
21 mm
23 mm
24 mm
26 mm
31 mm
37 mm
42 mm
46 mm
48 mm
16+20
16+20
16+25
16+32
16+40
16+50
16+63
16+63
9+11
9+13,5
9+16
9+21
9+29
9+36
9+42
9+48
24 mm
25 mm
27 mm
32 mm
37 mm
43 mm
46 mm
49 mm
M
PG
Distance
M
PG
Distance
20+20
20+25
20+32
20+40
20+50
20+63
20+63
M
11+13.5
11+16
11+21
11+29
11+36
11+42
11+48
PG
27 mm
29 mm
34 mm
40 mm
45 mm
48 mm
51 mm
Distance
20+25
20+32
20+40
20+50
20+63
20+63
13.5+16
13.5+21
13.5+29
13.5+36
13.5+42
13.5+48
30 mm
35 mm
41 mm
46 mm
49 mm
52 mm
25+32
25+40
25+50
25+63
25+63
16+21
16+29
16+36
16+42
16+48
37 mm
43 mm
48 mm
51 mm
54 mm
M
PG
Distance
M
PG
Distance
32+40
32+50
25+63
25+63
M
63+63
21+29
21+36
21+42
21+48
PG
42+48
50 mm
55 mm
58 mm
61 mm
Distance
73 mm
40+50
40+63
40+63
29+36
29+42
29+48
61 mm
64 mm
67 mm
50+63
50+63
36+42
35+48
69 mm
72 mm
Technical changes reserved.
Ensto Finland Oy
PEM804/REV A
© ENSTO 2014
3