GP 29 SGP 2 9 S OPEN VERSION - GP 29 GP 2 9

Transkrypt

GP 29 SGP 2 9 S OPEN VERSION - GP 29 GP 2 9
GP 29
EmergencyPowerSupply
Generating sets designed for both continous and stand-by mode
in case of mains failure.
GP Series units with PERKINS engines are rated as devices
with maximum durability, featured by highest level of
performance and reliability. Available power range from 606 to
2268 kVA.
kVA
29
STAND-BY ACTIVE POWER
kW
23
PRIME POWER
kVA
26
PRIME ACTIVE POWER
kW
21
NOMINAL CURRENT
A
38
VOLTAGE AVAILABLE
V
400/230
STEADY VOLTAGE PRECISION
%
±1
RATED FREQUENCY
Hz
50
FREQUENCY TOLERANCE
%
±0,5
OPEN VERSION - GP 29
GP 29
STAND-BY POWER
LENGTH
mm
1521
WIDTH
mm
760
HEIGHT
mm
1710
WEIGHT
kg
570
l
160L
dB
-
FUEL TANK
404D-22TG
TYPE
-
POWER
kW/hp
NO OF CYLINDERS, ARRANGEMENT
-
ASPIRATION TYPE
-
TOTAL DISPLACEMENT
l
2,216
ENGINE OIL CAPACITY
l
10,6
COOLING TYPE
-
LIQUID
COOLANT CAPACITY
l
9.3
ROTATIONAL SPEED
rpm
SPEED GOVERNOR
-
WIRING VOLTAGE
V
12
FUEL CONSUMTION at 75% load
l/h
5
FUEL CONSUMTION at 100% load
l/h
7,1
26,7
4L
TURBO
1500
Mechanical
CANOPIED VERSION - GP 29 S
LENGHT
mm
2200
WIDTH
mm
1000
HEIGHT
mm
1620
WEIGHT
kg
830
l
195
dB(A)
ok. 70dB
ALTERNATOR TYPE
-
MJL 160 SC4
PROTECTION RATING
-
IP23
REACTANCE Xd'
%
(puste)
THD at 100% load
%
(puste)
FUELTANK
INSULATION CLASS
-
(puste)
NOISE LEVEL AT 7 m
EPS SYSTEM Systemy Zasilania Awaryjnego
ul. Harcerska 16, 32 - 540 Trzebinia
tel. +48 32 623 66 88, fax +48 32 623 69 53
www.epssystem.pl, e-mail: [email protected]
GP 29 S
Marelli Alternator
Perkins Engine
NOISE
PROJECT & INSTALATION DATA FOR GENERATING SET
OPEN
CANNOPIED
RADIATOR HEIGHT
mm
514
RADIATOR WIDTH
mm
514
RADIATOR-BASE DISTANCE
mm
695,5
MIN. SURFACE OF AIR INLET
m2
0,34
MIN. SURFACE OF AIR OUTLET
m2
0,28
EXHAUST PIPE DIAMETER
mm
63.5/63.5
(puste)
CABLE MAX. CROSS-SECTION
mm2
(puste)
(puste)
Details above enable to project air circulation system in a premises designed for generating sets fitting. Exact size of air inlet and
outlet as well as cable minimal cross-section should be selected with taking gen-set location under consideration.
For open sets - outer radiator dimensions, pipe diameter exhaust coupler - muffler. For canopied sets - outer dimensions of air outlet fitted in the canopy.
Stand-By power (STAND-BY/LTP acc. to PN-ISO 8528)-power of the set using for emergency power suply; maximum power
available for a period of 500 hours/year with varying loads.
No kind of overload is permissible.
Prime power (PRP acc. to PN-ISO 8528)-maximum power available with varying loads for an unlimited number of hours. A 10%
overload is permissible for 1 hour every 12 hours of operation.
Open generating sets are to be put into premises or containers.
STANDARD OUTFIT
Canopied versions are resistant to weather and can be installed outside.
Engine and generator
Steel frame with vibration damping system
Cooling system and radiator
Control panels types:
Ignition battery, wiring system
- manual control panel;
Fuel tank, fuel system
-automatic control panel (turns on sets with volt-free contact);
Exhaust muffler and coupler-separated
- transfer switch panel with ATS (Automatic Transfer Switch)
Generator main switch
Automatic versions are normally equipped with engine block heater
and battery charger.
Control panel
Oil drainage pump
CANOPIED SETS ADDITIONAL EQUIPMENT
OPTIONS:
Varnished steel canopy
- container canopies made of steel, concrete or prefabricated;
Muffler fitted in a canopy
- certified towing trailers;
Easy access lockable door
- differential current switch;
Window for reading control devices
- 1 and 3-phase fused sockets;
External emergency stop button
- remote monitoring system of operation;
- volt-free contacts for operating conditions signalling;
- engine block heating system;
For more information about control panels please
look at separate folders.
Further information about canopies and gen-set
installation are available in additional booklet.
- battery charger;
- enlarged basic fuel tanks;
- external fuel tanks with re-filling system;
- muffler with enhanced attenuation degree;
- many canopy colours available (standard blue RAL5010).
Our products are constantly modified, so their appearance as well as some parameters may be slightly different to those enclosed in this leaflet. Presented pictures are samples only.
EPS SYSTEM Systemy Zasilania Awaryjnego ul. Harcerska 16, 32 - 540 Trzebinia
tel. +48 32 623 66 88, fax +48 32 623 69 53
www.epssystem.pl, e-mail: [email protected]