FLAME-PROOF INLET UNITS TYPE W_M,
THE BOOT TYPE ZW_
Ex d I Mb
Ex d IIB Gb, Ex t IIIC Da
KDB 06ATEX339U/1
1.
General description
Ex components – flame-proof inlet units with fastener type
W_M are designed for penetrations of wires/cables with
outer diameters of 6 ÷ 50 mm to flame-proof electric
appliances. Boots type ZW are designed for stopping
redundant openings in the inlet body.
2.
Usage conditions
Flame-proof inlet units type W_M, marked as follows
IM2 Ex d I Mb
II 2G Ex d IIB Gb
II 2D Ex t IIIC Da
IP 66
4.
Dimensions
are suitable for application
− in methane fields of coal mines, in excavations of
methane explosion hazard class a, b, or c, or coal
dust explosion hazard class A or B;
− indoors and outdoors in explosion hazard zones 1
and/or 2 and 21 and/or 22, where explosive mixtures
of gases, vapours, mists and flammable dust with air
can accumulate
3.
Compliance with standards
Flame-proof inlet units are manufactured in accordance
with principles of good safety engineering practice and are
state-of-the-art, to meet the requirements of the following
standards:
• PN-EN 60079-0: 2009 (EN 60079-0:2009),
• PN-EN 60079-1: 2010 (EN 60079-1: 2007),
• PN-EN 60079-31 :2010 (EN 60079-31:2009)
harmonized with EU Directive 94/9/EC, and the
regulations in force.
Bydgoskie Zakłady Elektromechaniczne
BELMA S.A.
ul. Łochowska 69, 86-005 Białe Błota
tel. (0-52) 36-36-201, fax. (0-52) 36-36-203; www.belma.com.pl, [email protected]
5.
Technical parameters
6.
Type of
entry unit
Range of wire/cable
outer diameters
/mm/
Type boot for
hole to blind
Skrew thread
according to PNISO 228-1:1995
W10M
Ф 6÷10
ZW10
G¾B
W20M
Ф 10÷20
ZW20
G 1⅛ B
W30M
Ф 20÷30
ZW30
G 1¾ B
W40M
Ф 30÷40
ZW40
G 2 ¼B
W50M
Ф 40÷50
ZW50
G 2½ B
Interchangeability
Flame-proof inlet units W-M marked: Ex d I Mb, Ex d IIB GB, Ex t IIIC Da IP 66 KDB 06ATEX339U or
Ex d I, Ex d IIB IP 66 can be used in place of inlet units:
type W-M and boots ZW_ marked Ex dI, Ex dIIB KDB 06ATEX339U
type W_M and boots ZW_ marked EEx dI/IIB KDB 04ATEX016U,
type W_M and boots ZW_ marked Ex dI/IIB KDB 06ATEX339U,
type WP-_ and boots type ZO_.
7.
Order example
In your order please specify the product designation
Example: Flame-proof inlet units type W20M.