MNL-11RFx MNL-13RFx
Transkrypt
MNL-11RFx MNL-13RFx
DO5 C5 3.3 DO1 24VAC DO2 DO3 24VAC DO4 Power: 24VAC, 50/60Hz, Class 2, 8.5VA + DO1-DO4 loads. Ambient Temp: -40°C to +60°C UI: 5VDC Max, Class 2. S-LK: 16VDC Max, Class 2. DO1-DO4: 24VAC, 0.4A Max Total Load. DO5: 250VAC, 3A Max, COS f = 0.4. 934G E9429 Temperature indicating and Regulating Equipment N2223 CAUTION T X M I J1 I/A Series MNL-11R GND 0V 24VAC UI3 COM 0V UI2 COM 0V UI1 S-LK S-LK LON LON SRVC S R R E V C C V DO7 C7 DO1 24VAC DO2 DO3 24VAC DO4 N2223 3.3 T X M I I/A Series ® MNL-13R Power: 24VAC, 50/60Hz, Class 2, 9.5VA + DO1-DO4 loads. Ambient Temp: -40°C to +55°C UI: 5VDC Max, Class 2 S-LK: 16VDC Max, Class 2 DO1-DO4: 24VAC, 0.4A Max Total Load. DO5-DO7: 250VAC, 3A Max, COS Φ = 0.4 J1 GND 0V 24VAC UI3 COM 0V UI2 COM 0V UI1 S-LK S-LK LON LON SRVC S R R E V C C V 934G E9429 Temperature indicating and Regulating Equipment CAUTION DO6 C6 DO5 C5 RISK OF ELECTRICAL SHOCK OR FIRE. DO NOT INTERCONNECT SEPARATE CLASS 2 CIRCUITS. DISCONNECT POWER BEFORE SERVICING. DECONNECTER AVANT ENTRETEN. This device conforms with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. This Class B digital apparatus meets all requirements of the Canadian InterferenceCausing Equipment Regulations. Cet appareil numerique de la classe B respecte toutes les exigences du Reglement F-26887-4 © Copyright 2006 TAC All Rights Reserved. Printed in U.S.A. 11-06 RISK OF ELECTRICAL SHOCK OR FIRE. DO NOT I N T E R C O N N E C T S E PA R AT E C L A S S 2 C I R C U I T S . D I S C O N N E C T P O W E R B E F O R E S E RV I C I N G . D E C O N N E C T E R AVA N T E N T R E T E N . TAC MicroNet Fan MNL-13RFx Coil Controller with Three High Voltage (MN 130) Relays • 3 Universal Inputs (software-configured) • 4 DO Triacs, capable of switching a total load of 0.5 A @ 24 Vac. • 3 DO Relay Outputs, 250 Vac, 3 A. • S-Link Support. MNL-13RFx TAC MicroNet Fan Coil Controller with One High Voltage Relay • 3 Universal Inputs (software-configured) • 4 DO Triacs, capable of switching a total load of 0.5 A @ 24 Vac. • 1 DO Relay Output, 250 Vac, 3 A. • S-Link Support. MNL-11RFx (MN 110) Inputs / Outputs Description Model This device conforms with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. This Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numerique de la classe B respecte toutes les exigences du Reglement sur le material brouilleur du Canada Model Chart MNL-11RFx The TAC I/A Series MNL-11RFx (MN 110) and MNL-13RFx (MN 130) Controllers are interoperable controllers designed in accordance with LONMARK® guidelines. When programmed using TAC WorkPlace Tech Tool, these controllers provide control for fan coil and unit ventilator applications. These controllers feature: screw terminal blocks; three universal inputs, software-configured to respond to one of five input types; one (MN 110) or three (MN 130) high-voltage relay output(s); four 24 Vac Triac (digital) outputs; and an S-Link interface for connection to an optional MN-Sx digital sensor. TAC I/A Series® MicroNet™ Fan Coil Controllers with High Voltage Relay(s) Installation Instructions TAC 1354 Clifford Avenue P. O. Box 2940 Loves Park, IL 61132-2940 www.tac.com MNL-11RFx MNL-13RFx Application The MN 110 and MN 130 controllers conform to the LONMARK Fan Coil Unit functional profile (8020) providing open communication and interoperability with third party LONMARK devices and greater freedom in system design. These controllers can function in standalone mode or as part of a LONWORKS® TP/FT-10 Free Topology network. Applicable Documentation F-Number Description F-26277 TAC I/A Series MicroNet MN-Sx Series Sensors General Instructions F-27255 TAC I/A Series WorkPlace Tech Tool 4.0 User’s Guide F-27254 TAC I/A Series WorkPlace Tech Tool 4.0 Engineering Guide F-26303 TAC I/A Series MicroNet System Overview F-26507 TAC I/A Series MicroNet Systems Engineering Guide F-26363 EN-206 Guidelines for Powering Multiple Full-Wave and Half-Wave Rectifier Devices from a Common Transformer Audience – – – – Purpose Application engineers Provides step-by-step installation, operation, and checkout procedures for TAC I/A Series MicroNet MN-Sx Series Sensors. Installers Start-up technicians Provides step-by-step instructions for using the TAC WorkPlace Tech Service personnel Tool. Reference for programming TAC MicroNet controllers, using the TAC – Application engineers WorkPlace Tech Tool. Gives detailed descriptions of all the Control – Service personnel Objects used with MN Series Controllers. – – – – Provides an overview of the TAC I/A Series MicroNet System. It includes brief descriptions of the hardware and software components, Application engineers and how they may be combined to create TAC MicroNet networks and Installers stand-alone systems. Start-up technicians Provides engineering and technical information to assist in designing Service personnel a complete TAC MicroNet controller system using different architectures, components, and software. Offers guidelines for avoiding equipment damage associated with – Application Engineers improperly wiring devices of varying rectifier types. Contains instructions for identifying device rectifier type, guidelines for correctly – Installers powering devices of varying rectifier types, and examples illustrating – Service Personnel proper power wiring techniques. INSTALLATION Inspection Requirements Inspect carton for damage. If damaged, notify carrier immediately. Inspect controllers for damage upon receipt. • Installer must be an experienced technician. • Tools: – Drill and bits – Digital Volt-ohm meter (DVM) – Static protection wrist strap • Class 2 power transformer supplying a nominal 24 Vac (20.4 to 30 Vac), 50/60 Hz. For transformer specifications, see the “Power Supply Wiring” section, on page 14. • Suitable grounded metal enclosure (to prevent the possibility of accidental contact with the high-voltage terminals) • Four #6 self-starting screws or 35 mm DIN rail for mounting • Terminators (if a TAC MicroNet LONWORKS network is used): – One LON-TERM1 terminator required for each free topology segment – Two LON-TERM2 terminators required for each bus topology segment • Accessories (as required): – MN-Sx TAC I/A Series MicroNet (S-Link) Sensors – 470k ohm 1/4 watt resistor (if shielded wire is used for S-Link wiring) – Approved Category 4 or 5, twisted-pair (two conductors) cable (optional LONWORKS Network connection) – 0.205 mm2 (#24 AWG) or larger twisted pair, voice grade telephone wire (for UI, AO, and DI wiring) – TSMN-57011-850 Series 10K ohm Thermistor Sensor with 11K ohm Shunt Resistor – TSMN-58011 Platinum Sensor – TSMN-81011 Balco Sensor – AD-8969-201 11K ohm Shunt Resistor Kit (if TSMN-57011-850 is not used) – 1K Balco or platinum element resistive sensor – 0 to 5 Vdc analog voltage transmitter – 4 to 20 mAdc analog current transmitter – Digital dry switched contact (switched contact resistance must be less than 300 ohms for closed contact and greater than 1.5K ohms for open contact) 2 © Copyright 2006 TAC All Rights Reserved. F-26887-4 Precautions General Warning: The MN 110 and MN 130 controllers are not suitable for exposed mounting on a wall or panel, or in any other easily accessible place due to the possibility of personal contact with the high-voltage terminals. They must be mounted inside a suitable grounded metal enclosure (Figure-2). Warning: Electrical shock hazard! Disconnect power from the controller and any digital outputs before installing or removing the cover. • Follow Static Precautions when installing this equipment. • Use copper conductors that are suitable for 75 °C (167 °F). • Make all connections according to electrical wiring diagram, national and local electrical codes. Static Precautions Static charges damage electronic components. The microprocessor and associated circuitry are extremely sensitive to static discharge. Use the following precautions when installing, servicing, or operating the system. • Work in a static-free area. • Discharge static electricity by touching a known, securely grounded object. • Use a wrist strap connected to earth ground when handling the controller’s printed circuit board. Federal Communications Commission (FCC) This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in residential installations. This equipment generates, uses, and can radiate radio frequency energy and may cause harmful interference if not installed and used in accordance with the instructions. Even when instructions are followed, there is no guarantee that interference will not occur in a particular installation. If this equipment causes harmful interference to radio or television reception — which can be determined by turning the equipment off and on — the user is encouraged to try to correct the interference by one or more of the following measures: • Reorient or relocate the receiving antenna. • Increase the separation between the equipment and receiver. • Connect the equipment to an outlet on a circuit different from that to which the receiver is connected. • Consult the dealer or an experienced radio/television technician for help. Canadian Department of Communications (DOC) Note: This Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numerique de la classe B respecte toutes les exigences du Reglement sur le material broilleur du Canada. European Community Directives This equipment meets all requirements of European Community Directives for Low Voltage (72/23/EEC), General Safety (92/59/EEC), and Electromagnetic Compatibility (89/336/EEC). Caution: • This is a Class A product. In a domestic environment this product may cause radio interference, in which case the user may be required to take adequate measures. • The LON and S-LK cables must be installed within grounded metallic conduit or conductive cable trays to fully comply with the EMC requirements of EN61326. F-26887-4 © Copyright 2006 TAC All Rights Reserved. 3 Location The MN 110 and MN 130 controllers are suitable for indoor use only (IP 20). See Figure-1 for mounting dimensions. When selecting a mounting location, make certain the following conditions are met: Warning: The MN 110 and MN 130 controllers are not suitable for exposed mounting on a wall or panel, or in any other easily accessible place due to the possibility of personal contact with the high-voltage terminals. They must be mounted inside a suitable grounded metal enclosure (Figure-2). Caution: • Do not install where excessive moisture, corrosive fumes, vibration, or explosive vapors are present. • Do not install near large contactors, electrical machinery, or welding equipment. • Allow 150 mm (6 in.) clearance from contactors, switches, and associated cabling. • Locate where ambient temperatures do not exceed 55 °C (131 °F) or fall below -40 °C (-40 °F) and relative humidity does not exceed 95%, non-condensing. 155 mm (6 in.) 14 mm (9/16 in.) 50 mm (2 in.) 132.5 mm (5-7/32 in.) 107 mm (4-3/16 in.) 95.5 mm (3-3/4 in.) 6 mm (1/4 in.) 134.5 mm (5-5/16 in.) 9 mm (3/8 in.) 23 mm (15/16 in.) Note: MN 110 shown. Dimensions are the same for MN 130. Figure-1 Mounting Dimensions. Mounting Panel or DIN Rail Mounting 1. Select a mounting location. Allow a minimum of 50 mm (2 in.) clearance around the controller. 4 © Copyright 2006 TAC All Rights Reserved. F-26887-4 Metal Enclosure 1 (Grounded) (4) Screws OR DIN Rail DO1 24VAC DO2 DO3 24VAC DO4 DO5 C5 N2223 UI3 GND 0V 24VAC LON S-LK S-LK S R V C J1 SRVC R E C V COM 0V UI2 COM 0V UI1 X M I T LON I/A Series MNL-11R 934G E9429 3.3 Temperature indicating and Regulating Equipment Controller (MN 110 Shown) Alternate Mounting Methods UI3 GND 0V 24VAC COM 0V UI2 COM 0V UI1 1 This example illustrates the use of a suitable grounded metal enclosure to mount an MN 110 or MN 130 controller. Dedicated Ground Wire from Enclosure This controller is not suitable for exposed mounting on a wall or panel, or in any other easily accessible place due to the possibility of personal contact with the high-voltage terminals. Grounding Point inside Enclosure Figure-2 Mounting in Enclosure. 2. Do the following to mount the controller onto a panel (Figure-3): a. Place the controller on a panel and mark the location of one top mounting hole. b. Drill the marked hole, using a drill bit sized for a #6 screw. c. Fasten the controller to the panel with one #6 self-starting screw. (1) Screw DO1 24VAC DO2 DO3 24VAC DO4 DO5 C5 DO1 24VAC DO2 DO3 24VAC DO4 DO5 C5 MNL-11R GND UI3 0V 24VAC COM 0V UI2 S-LK J1 LON LON S-LK S R V C SRVC R E C V COM 0V UI1 X M I T I/A Series 934G E9429 Temperature indicating and Regulating Equipment N2223 3.3 MNL-11R GND 0V 24VAC UI3 COM 0V UI2 J1 LON S-LK LON S-LK S R V C SRVC R E C V COM 0V UI1 X M I T I/A Series 934G E9429 Temperature indicating and Regulating Equipment N2223 3.3 (3) Screws Figure-3 Panel Mounting Method. d. Level the controller, then mark the locations of the remaining mounting holes. e. Drill the marked holes, then fasten the controller, using the three remaining screws. 3. Do the following to mount the controller onto a 35 mm DIN mounting rail (Figure-4): a. Hook the mounting tabs, on the back of the controller, onto the top edge of the DIN rail. b. Gently press the bottom of the controller onto the DIN rail so that it snaps into place. DO1 24VAC DO2 DO3 24VAC DO4 DO5 C5 DO1 24VAC DO2 DO3 24VAC DO4 DO5 C5 MNL-11R UI3 GND 0V 24VAC COM 0V UI2 LON S-LK LON S-LK S R V C J1 SRVC R E C V COM 0V UI1 X M I T I/A Series MNL-11R UI3 GND 0V 24VAC COM 0V UI2 LON S-LK S-LK S R V C J1 SRVC R E C V LON COM 0V UI1 X M I T I/A Series 934G E9429 3.3 934G E9429 3.3 Temperature indicating and Regulating Equipment N2223 N2223 Temperature indicating and Regulating Equipment Figure-4 DIN Rail Mounting Method. F-26887-4 © Copyright 2006 TAC All Rights Reserved. 5 Wiring The following electrical connections can be made to MN 110 and MN 130 controllers: • Communications wiring, including: • S-LK wiring between an MN 110 or MN 130 controller and an MN-Sx TAC I/A Series MicroNet Sensor. • TAC MicroNet LONWORKS network (LON) connection, including connections to other MNL-type TAC MicroNet controllers. • I/O connections, including: • Three Universal Inputs (UIs) • One (MN 110) or three (MN 130) high-voltage relay output(s) • Four Triac digital outputs • LONWORKS Network Jack • 24 Vac nominal class 2 (EN 60742) power source and earth ground power connection Ground GND 0V 24VAC UI3 COM 0V UI2 COM 0V UI1 S-LK S-LK LON LON DO1 24VAC DO2 DO3 Digital (Triac) Outputs 24VAC DO4 I/A Series MNL-11R DO1 24VAC DO2 DO3 GND 24VAC DO4 0V 24VAC UI3 Power: 24VAC, 50/60Hz, Class 2, 8.5VA + DO1-DO4 loads. Ambient Temp: -40°C to +60°C UI: 5VDC Max, Class 2. S-LK: 16VDC Max, Class 2. DO1-DO4: 24VAC, 0.4A Max Total Load. DO5: 250VAC, 3A Max, COS f = 0.4. COM 0V UI2 COM 0V UI1 S-LK S-LK 934G E9429 3.3 C5 TAC MicroNet LONWORKS Network Connection J1 N2223 DO5 TAC MicroNet Sensor Inputs LON LONWORKS Network (LON) Jack C5 High-Voltage Relay Universal Inputs LON Temperature indicating and Regulating Equipment DO5 24Vac Power (Transformer) SRVC X M I T CAUTION R E C V S R V C RISK OF ELECTRICAL SHOCK OR FIRE. DO NOT INTERCONNECT SEPARATE CLASS 2 CIRCUITS. DISCONNECT POWER BEFORE SERVICING. DECONNECTER AVANT ENTRETEN. Service Pin This device conforms with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. LEDs This Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numerique de la classe B respecte toutes les exigences du Reglement sur le material brouilleur du Canada Figure-5 MN 110 Terminal Connections. Ground DO1 Digital (Triac) Outputs 24VAC DO2 DO3 I/A Series® MNL-13R 24VAC DO1 DO4 DO2 DO3 24VAC Power: 24VAC, 50/60Hz, Class 2, 9.5VA + DO1-DO4 loads. Ambient Temp: -40°C to +55°C UI: 5VDC Max, Class 2 S-LK: 16VDC Max, Class 2 DO1-DO4: 24VAC, 0.4A Max Total Load. DO5-DO7: 250VAC, 3A Max, COS Φ = 0.4 GND 24VAC DO4 0V 24VAC UI3 COM 0V UI2 DO7 DO7 High-Voltage Relays C7 DO6 C6 DO5 C5 COM 0V UI1 C7 DO6 934G E9429 Temperature indicating and Regulating Equipment C6 S-LK S-LK LON N2223 LON 3.3 DO5 GND 0V 24VAC UI3 COM 0V UI2 COM 0V UI1 S-LK S-LK LON LON Universal Inputs TAC MicroNet Sensor Inputs TAC MicroNet LONWORKS Network Connection J1 C5 CAUTION RISK OF ELECTRICAL SHOCK OR FIRE. DO NOT INTERCONNECT SEPARATE CLASS 2 CIRCUITS. DISCONNECT POWER BEFORE SERVICING. DECONNECTER AVANT ENTRETEN. 24Vac Power (Transformer) SRVC X M I T R E C V S R V C This device conforms with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. This Class B digital apparatus meets all requirements of the Canadian InterferenceCausing Equipment Regulations. Cet appareil numerique de la classe B respecte toutes les exigences du Reglement LONWORKS Network (LON) Jack Service Pin LEDs Figure-6 MN 130 Terminal Connections. 6 © Copyright 2006 TAC All Rights Reserved. F-26887-4 Communications Wiring Communications wiring includes wiring between the MN 110 or MN 130 controller and one MN-Sx TAC I/A Series MicroNet Sensor, as well as wiring between the MN 110 or MN 130 controller and a TAC MicroNet LONWORKS Network (LON). For additional information on the TAC I/A Series MicroNet Sensors, including a list of available inputs, refer to the TAC I/A Series MicroNet Sensor General Instructions, F-26277. S-Link and LON Wiring Precautions Caution: • Communication wire pairs must be dedicated to S-Link and LON communications. They cannot be part of an active, bundled telephone trunk. • The LON and S-LK cables must be installed within grounded metallic conduit or conductive cable trays to fully comply with the EMC requirements of EN61326. • Shielded cable is not required for S-Link or LON communications wiring. If shielded wire is used, the shield must be connected to earth ground at only one end, using a 470k ohm 1/4 watt resistor, and the shield must be continuous from one end of the trunk to the other. • Conduit between a TAC I/A Series MicroNet Sensor and a controller can be shared by S-LK wiring and LON wiring, provided that this conduit does not also contain wiring for power, UI, AO, DI, or DO. However, the S-Link and LON wiring must be separate cables. Sensor Link (S-Link) Wiring Using S-LK wiring, an MN 110 or MN 130 controller may be connected to one MN-Sx TAC I/A Series MicroNet sensor. S-Link wiring powers and enables the sensor. The S-Link requires at least 0.205 mm2 (#24 AWG), twisted pair, voice-grade telephone wire. The capacitance between conductors cannot be more than 32 pF per 0.3 m (1 ft). If shielded cable is used, the capacitance between any one conductor and the others, connected to the shield, cannot be more than 60 pF per 0.3 m (1 ft). The maximum wire length is 61 m (200 ft). Note: • The MN 110 or MN 130 controller can support one MN-Sx TAC I/A Series MicroNet Sensor. • S-Link wiring is not polarity-sensitive. Connect the MN 110 or MN 130 controller to an MN-Sx TAC I/A Series MicroNet Sensor as follows: 1. Strip 6 mm (1/4 in.) of insulation from one end of the S-LK wires. 2. Connect the stripped wires to the S-LK terminals of the controller (Figure-5 or Figure-6). The S-LK connection is not polarity-sensitive. 3. Strip 6 mm (1/4 in.) of insulation from the other end of the S-LK wires. MN-Sx Series TAC I/A Series MicroNet Sensor MNL-11RFx MNL-13RFx 1 1 S-LK 1 S-LK 2 S-Link Terminals 1 The S-Link connection is not polarity sensitive. Figure-7 MN 110 and MN 130 S-Link Terminal Connections. 4. Connect the other end of the S-LK wires to the sensor, according to the TAC I/A Series MicroNet Sensor General Instructions, F-26277. F-26887-4 © Copyright 2006 TAC All Rights Reserved. 7 TAC MicroNet LONWORKS Network (LON) Wiring Approved Category 4 or 5, twisted-pair (two conductors) cable may be used for the LONWORKS Network connection between the MN 110 or MN 130 controller and a TAC MicroNet LONWORKS Network, or for the optional LONWORKS Network connection between the controller and an MN-Sx TAC I/A Series MicroNet Sensor. Caution: • See the section, “S-Link and LON Wiring Precautions,” on page 7. • Do not mix LON network wiring with power, UI, AO, DI, or DO types of wiring. • Conduit between an MN-Sx TAC I/A Series MicroNet Sensor and a controller can be shared by LON wiring and S-LK wiring, provided that this conduit does not also contain wiring for power, UI, AO, DI, or DO. However, the S-Link and LON wiring must be separate cables. Note: For complete details on designing and wiring TAC MicroNet networks, including approved cable models, refer to the TAC I/A Series MicroNet System Engineering Guide, F-26507. Connect the MN 110 or MN 130 controller to a TAC MicroNet LONWORKS Network or an MN-Sx TAC I/A Series MicroNet Sensor as follows: 1. Strip 6 mm (1/4 in.) of insulation from one end of the LON wires. 2. Connect the stripped wires to the LON terminals of the controller (Figure-8). The LON connection is not polarity-sensitive. 3. Strip 6 mm (1/4 in.) of insulation from the other end of the LON wires. MNL-11RFx MNL-13RFx 1 LON LON TAC MicroNet LONWORKS Network 1 The LONWORKS connection is not polarity sensitive. Figure-8 MN 110 and MN 130 LONWORKS Network Terminal Connections. 4. If the MN 110 or MN 130 controller is to be connected to a LONWORKS network, determine the topology chosen for the TP/FT-10 segment, then connect to additonal controllers. To allow the MN 110 or MN 130 to share data with other LONWORKS devices, the controller must be addressed and the desired network bindings must be made. Refer to the section, “Installation on a LONWORKS Network,” to accomplish this. Note: • The MN 110 and MN 130 controllers use the LONWORKS Free Topology Transceiver (FT 3150®). It may be connected to other controllers freely, using multiple wiring tees and stars (Free Topology) or using a daisy-chain topology. If a daisy-chain topology is chosen, the controllers must be connected only in a device-to-device fashion (Bus Topology). A maximum of 62 nodes can be connected per wiring segment. • See the TAC I/A Series MicroNet System Engineering Guide, F-26507, to design a TAC MicroNet LONWORKS TP/FT-10 network, including recommended topologies and approved cable types. 5. If the MN 110 or MN 130 controller is to be wired to a TAC MicroNet sensor, make the LONWORKS Network connection according to the TAC I/A Series MicroNet Sensor General Instructions, F-26277. 8 © Copyright 2006 TAC All Rights Reserved. F-26887-4 Note: • Use of the LON terminals to connect to the MN-Sx sensor permits use of the sensor’s built-in LONWORKS Network Jack. • To preserve the integrity of the network, the LONWORKS Network wiring connecting a TAC I/A Series MicroNet controller to an MN-Sx sensor must be run to the sensor and back, in daisy-chain fashion. A wire “spur” must not be used to connect the sensor to the controller. • While the MN-Sx sensor is not counted as a “node” in the LONWORKS Network (LON), all LONWORKS Network wiring to the sensor must be counted when determining the length of the TP/FT-10 wiring segment. 6. Install terminators as required. I/O Wiring I/O connections include three software-configured universal inputs (UIs), one (MN 110) or three (MN 130) high-voltage relay output(s) (DOs), and four Triac outputs. The Triac outputs are for switching 24 Vac pilot-duty loads. See Figure-5 and Figure-6 for wire terminal information. Warning: Electrical shock hazard. Remove all power from both the controller and digital outputs before making terminations. UI, AO, and DI wiring require at least 0.205 mm 2 (#24 AWG), twisted pair, voice grade telephone wire. The capacitance between conductors cannot be more than 32 pF per 0.3 m (1 ft). If shielded cable is used, the capacitance between any one conductor and the others, connected to the shield, cannot be more than 60 pF per 0.3 m (1 ft). Refer to Table-1 for wiring specifications. Table-1 UI, AO, and DI Wiring Specifications. Connection UI, AO, and DI Gage mm2 (AWG) Maximum Distance m (ft) 0.823 (18) 91 (300) 0.518 (20) 61 (200) 0.326 (22) 38 (125) 0.205 (24) 23 (75) Universal Inputs (UI) The Universal Inputs’ characteristics are software-configured to respond to one of the following input types: 1. 10K ohm Thermistor with 11K ohm Shunt Resistor (refer to Figure-9). 2. 10K ohm Resistive. 3. 1K ohm Balco (refer to Figure-10). 4. 1K ohm Platinum (refer to Figure-10). 5. 1K ohm Resistive. 6. Analog Voltage (refer to Figure-11). 7. Analog Current (refer to Figure-12). 8. Digital Dry Switched Contact (refer to Figure-13). Caution: • If shielded cable is used for universal inputs (UI), connect only one end of the shield to a single COM 0V terminal (not to GND). • If shielded cable is used for other I/O, connect only one end of the shield to a single earth ground point, at the controller’s ground (GND) terminal. • Input and output devices cannot share common wiring. Each connected device requires a separate signal and return conductor. • UI, S-Link, and LON wiring cannot share a conduit with either power wiring or high-voltage relay wiring. F-26887-4 © Copyright 2006 TAC All Rights Reserved. 9 Note: UI and S-Link wiring can share a single conduit. 10K Thermistor with 11K Shunt Resistor Any of the MN 110 or MN 130 controller’s UI inputs can be configured for Thermistor input. When configured in this way, a 10K ohm Thermistor with 11K ohm shunt resistor (TAC TSMN-57011-850) may be connected to the MN 110 or MN 130 controller to sense the space temperature. See Table-2 for temperature versus resistance data for this thermistor. Table-2 Temperature Versus Resistance for TSMN-57011-850 Thermistor. Temperature °C (°F) Resistance ohms Temperature °C (°F) Resistance ohms 4 (40) 7596 30 (86) 4696 10 (50) 6938 40 (104) 3707 20 (68) 5798 50 (122) 2875 25 (77) 5238 60 (140) 2206 Make the Thermistor connections according to the diagram in Figure-9. MNL-11RFx MNL-13RFx 1 UI1 COM 0V TSMN-57011-850 1 Any one of the three Universal Inputs (UI1, UI2, or UI3) may be programmed for Thermistor input. Connection to UI1 is illustrated here as an example only. 2 Applications that use a non-850 series 10K thermistor sensor require an 11K ohm Shunt Resistor Kit, AD-8969-206. Install this resistor across the Universal Input and the Common. 2 1 10K ohm Thermistor 2 11K ohm ± 0.1% Shunt Resistor Figure-9 Typical Wiring for 10K Thermistor with 11K Shunt Resistor (TSMN-57011-850). Resistive — 1K Balco or 1K Platinum Input Any of the MN 110 or MN 130 controller’s UI inputs can be configured for the 1K Balco or Platinum Element Resistive Sensor. Make the connections according to the diagram in Figure-10. MNL-11RFx MNL-13RFx 1 1K Resistive Sensor Balco or Platinum Element UI1 COM 0V 1 Any one of the three Universal Inputs (UI1, UI2, or UI3) may be programmed for Balco or Platinum Sensor input. Connection to UI1 is illustrated here as an example only. Figure-10 Typical Wiring for 1K Balco or 1K Platinum Sensor Input. 10 © Copyright 2006 TAC All Rights Reserved. F-26887-4 Analog Voltage Input Any of the MN 110 or MN 130 controller’s UI inputs can be configured for the 0 to 5 Vdc Analog Voltage Transmitter input. Make the connections according to the diagram in Figure-11. MNL-11RFx MNL-13RFx 1 0 to 5 Vdc Transmitter Power Source + UI1 COM 0V _ 1 Any one of the three Universal Inputs (UI1, UI2, or UI3) may be programmed for 0 to 5 Vdc Analog Voltage input. Connection to UI1 is illustrated here as an example only. 2 Input signals of 1 to 11 Vdc must be converted to 0.45 to 5 Vdc with a Voltage Divider, AD-8961-220. Figure-11 Typical Wiring for 0 to 5 Vdc Analog Voltage Input. Analog Current Input Any of the MN 110 or MN 130 controller’s UI inputs can be configured for the 4 to 20 mAdc Analog Current Transmitter input. Make the connections according to the diagram in Figure-12. MNL-11RFx MNL-13RFx 1 4 to 20 mA Transmitter + UI1 250 ohm 2 COM 0V Power Source 1 Any one of the three Universal Inputs (UI1, UI2, or UI3) may be programmed for 4 to 20 mAdc Analog Current input. Connection to UI1 is illustrated here as an example only. 2 Input signals of 4 to 20 mAdc must be converted to 1 to 5 Vdc with a 250 ohm Shunt Resistor Kit, AD-8969-202. Install the resistor across the Universal Input and Common terminals. _ Figure-12 Typical Wiring for 4 to 20 mA Analog Current Input. Digital Dry Switched Contact Input Any of the MN 110 or MN 130 controller’s UI inputs can be configured for the Digital Dry Switched Contact input. Make the connections according to the diagram in Figure-13. Note: If the maximum closed switch voltage is not more than 1.0 V and the minimum open switch voltage is at least 4.5 V, then solid state switches may be used for a UI when configured as a DI. MNL-11RFx MNL-13RFx 1 Digital Dry Switched Contact UI1 1 Any one of the three Universal Inputs (UI1, UI2, or UI3) may be programmed for Digital Dry Switched Contact input. Connection to UI1 is illustrated here as an example only. 2 Switched contact resistance must be less than 300 ohms for closed contact and greater than 1.5K ohms for open contact. 2 COM 0V Figure-13 Typical Wiring for Digital Dry Switched Contact Input. F-26887-4 © Copyright 2006 TAC All Rights Reserved. 11 Digital Triac Outputs (DOs) The MN 110 and MN 130 controllers contain four 24 Vac (digital) Triac outputs. Before wiring these outputs, refer to Table-3 for their electrical specifications. Table-3 Triac Output Electrical Specifications. Characteristic Specification Maximum Triac Switched Output Voltage 24 Vac terminal voltage a Minimum Triac Switched Output Voltage 24 Vac terminal voltage a - 2.0 Vac Rating 12 VA (0.5 A) @ 24 Vac at each output. Total of 12 VA @ 24 Vac for all outputs that are ON at any one time. Motor Requirements NA Default Output State OFF (inactive) Output Short Circuit Protection Internal current limiting Maximum Off-State Leakage Current 2.0 mA Minimum Permissible Load 50 mA a Switched output voltage is equivalent to the value of the input voltage. Caution: • Do not mix DO wiring with power, high-voltage relay, DI, UI, S-Link, LON, or AO wiring. • The total output load for DO1 through DO4 is 12 VA. This limit applies whether one, two, three, or all four DOs are ON at the same time. Exceeding this limit may result in the loss of controller power until the external fault is removed and the internal PTC (Positive Temperature Coefficient) device cools sufficiently. The PTC is a current-limiting thermal safety device. Triac output terminals accept one 0.823 mm2 (#18 AWG) or smaller wire. The selected wire gage must be consistent with the load current rating. • Note: • DO1 through DO4 are Triac outputs for switching 24 Vac loads only, such as pilot-duty relays and floating control actuators. • Triac outputs switch the load circuit to ground and are supplied through the 24VAC terminals. Connect the MN 110 or MN 130 controller’s Triac output terminals (DO1, DO2, DO3, and DO4) as follows: 1. Connect one side of a 24 Vac load to one of the 24VAC terminals. Caution: Whenever the MN 110 or MN 130 is connected to share I/O with other controllers, care must be exercised to connect the power for the inputs in a consistent manner. Refer to the wiring diagram on the cover. 2. Connect the other side of the load to a Triac output terminal (DO1, DO2, DO3, or DO4). See Figure-14. 24 Vac Load (Cooling) Open B3 1 COM R1 MNL-11RFx MNL-13RFx DO1 24Vac Close W2 DO2 24 Vac Load (Heating) Open B3 DO3 1 COM R1 Close W2 24Vac DO4 0V 24Vac 1 The example shown here is for controlling two 24 Vac floating valve actuators (e.g. MF-631x3 Series). Figure-14 24 Vac Loads Switched by Triac Outputs. 12 © Copyright 2006 TAC All Rights Reserved. F-26887-4 High-Voltage Relay Output The MN 110 controller contains one high-voltage relay output and the MN 130 controller contains three such outputs. Before wiring a high-voltage output, refer to Table-4 for its electrical specifications. Table-4 High-Voltage Relay Output Load Specifications. Specification Value Maximum Relay Contact Switched Output Voltage 250 Vac Maximum Output Load (cos φ = 0.4) 3.0 A Minimum Controllable Load @ 5 Vdc 10.0 mA Maximum Off-State Leakage Current 100 µA Minimum Cycles at Rated Load @ 0.4 Power Factor 100,000 cycles Caution: • Do not mix high-voltage relay wiring with any other controller wiring. • High-voltage relay terminals accept one 2.08 mm2 (#14 AWG) or smaller wire. The selected wire gage must be consistent with the load current rating. Connect the MN 110 or MN 130 controller’s high-voltage relay terminal(s) (DO5 and C5 for the MN 110; DO5, C5, DO6, C6, DO7, and C7 for MN 130) to 230 Vac power and the switched 230 Vac motor(s) as shown in Figure-15 and Figure-16. MNL-11RFx 230 Vac 3A Motor DO5 C5 230 Vac Power Figure-15 MN 110 Connection to 230 Vac High-Voltage Relay. MNL-13RFx 230 Vac 3A Motor #3 DO7 C7 230 Vac Power DO6 230 Vac 3A Motor #2 C6 230 Vac Power DO5 230 Vac 3A Motor #1 C5 230 Vac Power Figure-16 MN 130 Connections to 230 Vac High-Voltage Relays. F-26887-4 © Copyright 2006 TAC All Rights Reserved. 13 Power Supply Wiring Power Supply Wiring Precautions Caution: • The MN 110 and MN 130 controllers contain a non-isolated half-wave rectifier power supply and must not be powered by transformers used to power other devices containing non-isolated full-wave rectifier power supplies. Refer to EN-206, Guidelines for Powering Multiple Full-Wave and Half-Wave Rectifier Devices from a Common Transformer, F-26363, for detailed information. • Do not mix power wiring or high-voltage relay wiring with any other controller wiring. • Use a Class 2 power transformer supplying a nominal 24 Vac (20.4 to 30 Vac), 50/60 Hz. It must have a minimum rating of 9.5 VA plus the DO1 through DO4 total output load of 12 VA maximum, up to a total of 21.5 VA per controller. In the European Community, a safety-isolating SELV (Safety Extra Low-Voltage), limited energy source (<100 VA) transformer that conforms to EN 60742 must be used. • The transformer frame must be grounded, and the supply to the transformer must have a circuit breaker or disconnect. Note: • 24 Vac power wiring can be intermixed with DO wiring. • Twisted or untwisted cable can be used for power wiring. • To preserve the integrity of the network, the LONWORKS Network wiring connecting a TAC I/A Series MicroNet controller to an MN-Sx sensor must be run to the sensor and back, in daisy-chain fashion. A wire “spur” must not be used to connect the sensor to the controller. Power Wiring Refer to Figure-17 and Figure-18 for acceptable wiring configurations. 1. Connect the power ground wire to the Ground terminal (GND). 2. Connect the 24 Vac power wiring to the power terminals (24 VAC and 0V). 24 Vac Secondary Class 2 Primary S-Link MN-Sx Sensor 1 LON LON LON S-LK S-LK 0V 24VAC GND 2 MNL-11RFx MNL-13RFx To rest of the LONWORKS network 1 Optional connection provides local access to the LONWORKS network. 2 Ground the frame of the transformer to a known ground. Figure-17 Power Supply Connection — Single Controller Powered from a Separate Class 2 Power Source. 14 © Copyright 2006 TAC All Rights Reserved. F-26887-4 To other TAC MicroNet LONMARK and LONWORKS Controllers 24 Vac Secondary Class 2 Primary To rest of the LONWORKS network S-Link MN-Sx Sensor LON LON S-LK S-LK 0V 24VAC GND 2 LON 1 MNL-11RFx MNL-13RFx 3 S-Link LON LON S-LK S-LK 24VAC 0V GND MN-Sx Sensor LON 1 MNL-11RFx MNL-13RFx S-Link 1 LON LON S-LK LON S-LK 24VAC 0V GND MN-Sx Sensor MNL-11RFx MNL-13RFx S-Link 1 LON Class 2 wiring. LON 3 S-LK Ground the frame of the transformer to a known ground. LON S-LK 2 24VAC Optional connection provides local access to the LONWORKS network. 0V 1 GND MN-Sx Sensor MNL-11RFx MNL-13RFx To rest of the LONWORKS network Figure-18 Power Supply Connection — Multiple Controllers Powered from a Separate Class 2 Power Source and Sharing Communications in a Free Topology Segment. F-26887-4 © Copyright 2006 TAC All Rights Reserved. 15 Installation on a LONWORKS Network In addition to functioning in standalone mode, the MN 110 or MN 130 controller may be connected to a LONWORKS network for data sharing with other LONWORKS devices. This is made possible by addressing the controller on the network and performing the desired network bindings. LONWORKS Network Addressing Address the controller on the LONWORKS network, as follows: 1. Verify that the controller is powered and connected to the network. 2. Perform the necessary steps to configure the controller, using the TAC WorkPlace Tech Tool (WP Tech). This involves the creation and downloading of control logic to the controller. Refer to the TAC WorkPlace Tech Tool 4.0 User’s Guide, F-27255. Note: The TAC WorkPlace Tech Tool must be Version 4.0 or greater when it is used to configure the MN 110 and MN 130 controllers on a LONWORKS network. 3. Using an appropriate network management tool, proceed to address the controller on the LONWORKS network, up to the point at which the tool asks for the controller’s unique Neuron® ID. This address will consist of a domain, subnet, and node. 4. Obtain the controller’s Neuron ID, using either of the following methods: Service Pin Button a. Make the network tool “listen” for the service pin message. b. Press and release the controller’s service pin button. This sends a broadcast message containing the controller’s Neuron ID (the controller’s LONWORKS serial number). Service pin messages can be sent from a controller, whether addressed or not, as many times as necessary. Caution: Do not hold the service pin button in the pressed position. Holding the service pin button for 6 seconds or longer will completely unconfigure the controller. Note: If an MN-S2, MN-S3, MN-S4, or MN-S5 sensor is connected to the controller, the sensor’s override button can also be used to generate a service pin message from the controller. For more information, refer to the TAC I/A Series MicroNet Sensor General Instructions, F-26277. Manual Method a. Indicate to the network tool that you will enter the Neuron ID manually. b. Locate the controller’s Neuron ID. The MN 110 or MN 130 controller’s Neuron ID is printed on a pair of barcode labels attached to the controller at the factory. One of the labels remains on the controller permanently, while the other label can be detached and placed on a job site’s node list plan. c. Manually enter the Neuron ID into the tool, or scan the barcode. 5. Proceed to finish commissioning the controller on the LONWORKS network. Network Bindings Using an appropriate network management tool, perform the desired network bindings to enable the sharing of data over the LONWORKS network. Refer to the TAC I/A Series WorkPlace Tech Tool 4.0 Engineering Guide, F-27254, for information on the network variables available in the MN 110 or MN 130 controller’s Fan Coil profile. 16 © Copyright 2006 TAC All Rights Reserved. F-26887-4 Checkout Mechanical Hardware Checkout 1. If an MN-Sx TAC I/A Series MicroNet Sensor is connected to the controller, verify that the wiring between the sensor and the controller is installed according to the job wiring diagram and national and local wiring codes. Note: Wiring of the S-Link and TAC MicroNet LONWORKS network between the sensor and the controller is not polarity sensitive. 2. If the controller is part of a TAC MicroNet LONWORKS network, verify that the TP/FT-10 LONWORKS network wiring between the controller and other devices is installed according to the job wiring diagram and the national and local electrical codes. 3. Verify that 24 Vac power is provided from a Class 2 power transformer, and that wiring is installed according to the job wiring diagrams and the national and local electrical codes. 4. If multiple devices are powered from the same transformer (Figure-18), verify that wiring polarity has been maintained between all connected devices, and that all other issues associated with powering multiple devices from a common transformer have been addressed. Note: For more information, refer to EN-206, Guidelines for Powering Multiple Full-Wave and Half-Wave Rectifier Devices from a Common Transformer, F-26363. 5. Verify that the digital outputs and the high-voltage relay(s) are wired according to the job wiring diagram and the national and local electrical codes. 6. Make certain that the current requirements of the controlled device do not exceed the rating of the controller’s digital outputs. Communications Hardware Checkout In addition to functioning in standalone mode, the MN 110 or MN 130 controller may be connected to a LONWORKS network for data sharing with other LONWORKS devices. If so, check the status of its network communications according to the following procedure: 1. Verify that all controlled equipment is in a manually controlled, safe state. 2. Place the controller’s power circuit breaker in the ON position. See the job wiring diagrams for the location of this breaker. 3. Observe the green Data Transmission LED (Figure-19) and do the following: a. If the green Data Transmission LED is steady ON or blinking, go to step 4. b. If the green Data Transmission LED is OFF, check the power to the controller. 4. Observe the red Service LED (Figure-19) and do the following: a. If the red Service LED is off or flashing, proceed with downloading an application using TAC WorkPlace Tech Tool and configuring the controller with a third party network management tool. Refer to TAC WorkPlace Tech Tool 4.0 Engineering Guide, F-27254, for details on downloading applications. b. If the red Service LED is steady ON, turn OFF the power to the controller, wait five seconds, then turn the power ON. If the red Service LED is still steady ON, turn the power OFF and replace the controller. 5. If necessary, perform additional checks and take the appropriate corrective action, according to Table-5. F-26887-4 © Copyright 2006 TAC All Rights Reserved. 17 Power and Data Transmission LED (Green) Data Reception LED (Amber) LONWORKS Network Jack Service LED (Red) Service Pin Figure-19 Location of Controller LEDs. 18 © Copyright 2006 TAC All Rights Reserved. F-26887-4 Table-5 LED Indication. Indicator Data Reception LED – amber Context Anytime Status Corrective Action Blinks when the controller receives data from the LONWORKS Network. None required. On indicates a possible network connection problem, or a large amount of network traffic is present. Remove the LONWORKS Network connections from the controller and determine if the LED goes off. If the LED does not go off, replace the controller. If the LED does go off, check the network topology (connections to each node, routers, terminators, etc.) and the amount of traffic on the network. Off indicates that data reception is not taking place. Blinks when the controller transmits data to the LONWORKS Network. Data Transmission LED – Green Anytime Off indicates no power to controller. Check power Power-up The LED blinks once to indicate successful power-up. Wink mode Blinks (3 seconds on, 1 second off) three times to indicate physical location of the controller. If a sensor (MN-Sx) is connected, its red occupancy LED will flash (1/sec) during the wink period. Anytime On indicates that the neuron application is not running. Neuron applications are not field replaceable. Replace the controller. Blinks (1/sec) to indicate that the neuron application is loaded, but the neuron’s communication parameters are not loaded, are being reloaded, or have been corrupted. Neuron is considered unconfigured. Communication parameters cannot be configured by field personnel. Use a third party network management tool to commission the controller, or use the change state tool in TAC WorkPlace Tech Tool (version 4.0 or greater) to set the Neuron® to the configured/on-line state. While the controller is unconfigured, WP Tech can be used to download an application, but at the completion of the download, WP Tech versions 4.0 and higher will restore the Neuron to the unconfigured state. Anytime Off may indicate that the neuron application is loaded but the device is off-line. In this state, a pre-loaded HVAC application will not run. Use a third party network management tool to commission the controller, or use the change state tool in TAC WorkPlace Tech Tool (version 4.0 or greater) to set the Neuron to the configured/on-line state. While the controller is off-line, WP Tech can be used to download an application, but at the completion of the download, WP Tech versions 4.0 and higher will restore the Neuron to the off-line state. Anytime Off usually indicates a normal state. In this state, the controller operates normally, and you can download and/or run HVAC applications. If the controller is able to accept and/or run a downloaded HVAC application, no action is required. Anytime Service LED – Red F-26887-4 None Required On indicates that the controller is not transmitting data. On also indicates that power is being applied to the controller. © Copyright 2006 TAC All Rights Reserved. None Required 19 Service Components within the MN 110 and MN 130 controllers cannot be field repaired. If there is a problem with the controller, follow the steps outlined in the “Checkout“ section. If the problem persists, record the following hardware setup information before contacting your local Invensys Building Systems office: • • • • Copyright 2006, TAC All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. Version number of the application software. The controller’s firmware version number. Information regarding the network management tool being used. A complete description of the difficulties encountered. TAC 1354 Clifford Avenue P.O. Box 2940 Loves Park, IL 61132-2940 F-26887-4 www.tac.com Distributed, manufactured, and sold by TAC. I/A SERIES trademarks are owned by Invensys Systems, Inc. and are used on this product under master license from Invensys. Invensys does not manufacture this product or provide any product warranty or support. For service, support, and warranty information, contact TAC at 1-888-444-1311.