LA 200-P Przetwornik prądowy | LEM - DACPOL : SKLEP
Transkrypt
LA 200-P Przetwornik prądowy | LEM - DACPOL : SKLEP
IPN Current Transducer LF 2005-S = 2000 A For the electronic measurement of currents : DC, AC, pulsed..., with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit). 16103 Electrical data IPN IPM RM Primary nominal current rms Primary current, measuring range @ ± 24 V Measuring resistance @ TA = 70°C RM minRM max with ± 15 V @ ± 2000 A max @ ± 2200 A max with ± 24 V @ ± 2000 A max @ ± 3000 A max Secondary nominal current rms Conversion ratio Supply voltage (± 5 %) Current consumption (± 1) ISN KN VC IC 0 0 5 5 8 5 29 11 2000 0 .. ± 3000 TA = 85°C RM minRM max A A • Closed loop (compensated) current transducer using the Hall effect 0 7 Ω 0 4 Ω 13 28 Ω @ ± 2800 A 13 13 Ω 400 mA 1 : 5000 ± 15 .. 24 V 33 (@ ± 24 V) + IS m A Accuracy - Dynamic performance data X ε Accuracy @ IPN , TA = 25°C Linearity error L ± 0.3 < 0.1 Typ IO IOM IOT tr di/dt BW Offset current @ IP = 0, TA = 25°C Magnetic offset current @ IP = 0 and specified RM, after an overload of 3 x IPN Temperature variation of IO - 25°C .. + 85°C - 40°C .. - 25°C Response time 1) to 90 % of IPN step di/dt accurately followed Frequency bandwidth (- 1 dB) ± 0.2 % % Max ± 0.5 ± 0.2 ± 0.5 ± 1.5 <1 > 50 DC .. 100 Features mA mA mA mA µs A/µs kHz • Isolated plastic case recognized according to UL 94-V0. Advantages • • • • • • • Excellent accuracy Very good linearity Low temperature drift Optimized response time Wide frequency bandwidth No insertion losses High immunity to external interference • Current overload capability. Applications • AC variable speed drives and servo motor drives • Static converters for DC motor drives • Battery supplied applications • Uninterruptible Power Supplies (UPS) • Switched Mode Power Supplies (SMPS) • Power supplies for welding General data applications. TA TS RS Ambient operating temperature Ambient storage temperature Secondary coil resistance m Mass Standards Note: 1) @ TA = 70°C @ TA = 85°C - 40 .. + 85 °C - 50 .. + 90 °C 25 Ω 26 Ω 1.5 kg EN 50178: 1997 Application domain • Industrial. With a di/dt of 100 A/µs. Page 1/3 080711/9 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice. w w w .lem.com Current Transducer LF 2005-S Isolation characteristics Vd Rms voltage for AC isolation test, 50 Hz, 1 min 6 kV dCp dCl CTI Creepage distance Clearance distance Comparative Tracking Index (Group I) Min 29.1 27.1 600 mm mm Application examples According to EN 50178 and IEC 61010-1 standards and following conditions : • Over voltage category OV 3 • Pollution degree PD2 • Non-uniform field EN 50178 IEC 61010-1 Rated isolation voltage Nominal voltage Single isolation 4000 4000 Reinforced isolation 2000 2000 dCp, dCI Safety This transducer must be used in electric/electronic equipment with respect to applicable standards and safety requirements in accordance with the manufacturer's operating instructions. Caution, risk of electrical shock When operating the transducer, certain parts of the module can carry hazardous voltage (eg. primary busbar, power supply). Ignoring this warning can lead to injury and/or cause serious damage. This transducer is a built-in device, whose conducting parts must be inaccessible after installation. A protective housing or additional shield could be used. Main supply must be able to be disconnected. Page 2/3 080711/9 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice. w w w .lem.com Dimensions LF 2005-S (in mm. 1 mm = 0.0394 inch) Left view Front view Connection Top view Mechanical characteristics Remarks • General tolerance • Fastening transducer • IS is positive when IP flows in the direction of the arrow. • Temperature of the primary conductor should not exceed Flat or vertical position Recommended fastening torque • Primary through-hole Or • Connection of secondary ± 0.5 mm 4 holes ∅ 6.5 mm 4 M6 screw steel 5.5 Nm or 4.05 Lb. - Ft. 60.5 x 20.5 mm ∅ max 57 mm S3P-VH 100°C. • Dynamic performances (di/dt and response time) are best with a single bar completely filling the primary hole. • This is a standard model. For different versions (supply voltages, turns ratios, unidirectional measurements...), please contact us. Page 3/3 080711/9 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice. w w w .lem.com