LA 200-P Przetwornik prądowy | LEM - DACPOL : SKLEP

Transkrypt

LA 200-P Przetwornik prądowy | LEM - DACPOL : SKLEP
IPN
Current Transducer LF 2005-S
=
2000 A
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
16103
Electrical data
IPN
IPM
RM
Primary nominal current rms
Primary current, measuring range @ ± 24 V
Measuring resistance @
TA = 70°C
RM minRM max
with ± 15 V
@ ± 2000 A max
@ ± 2200 A max
with ± 24 V @ ± 2000 A max
@ ± 3000 A max
Secondary nominal current rms
Conversion ratio
Supply voltage (± 5 %)
Current consumption (± 1)
ISN
KN
VC
IC
0
0
5
5
8
5
29
11
2000
0 .. ± 3000
TA = 85°C
RM minRM max
A
A
• Closed loop (compensated) current
transducer using the Hall effect
0
7
Ω
0
4
Ω
13 28
Ω
@ ± 2800 A 13 13
Ω
400
mA
1 : 5000
± 15 .. 24
V
33 (@ ± 24 V) + IS m A
Accuracy - Dynamic performance data
X
ε
Accuracy @ IPN , TA = 25°C
Linearity error
L
± 0.3
< 0.1
Typ
IO
IOM
IOT
tr
di/dt
BW
Offset current @ IP = 0, TA = 25°C
Magnetic offset current @ IP = 0 and specified RM,
after an overload of 3 x IPN
Temperature variation of IO - 25°C .. + 85°C
- 40°C .. - 25°C
Response time 1) to 90 % of IPN step
di/dt accurately followed
Frequency bandwidth (- 1 dB)
± 0.2
%
%
Max
± 0.5
± 0.2
± 0.5
± 1.5
<1
> 50
DC .. 100
Features
mA
mA
mA
mA
µs
A/µs
kHz
• Isolated plastic case recognized
according to UL 94-V0.
Advantages
•
•
•
•
•
•
•
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
• Current overload capability.
Applications
• AC variable speed drives and servo
motor drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Switched Mode Power Supplies
(SMPS)
• Power supplies for welding
General data
applications.
TA
TS
RS
Ambient operating temperature
Ambient storage temperature
Secondary coil resistance
m
Mass
Standards
Note:
1)
@ TA = 70°C
@ TA = 85°C
- 40 .. + 85
°C
- 50 .. + 90
°C
25
Ω
26
Ω
1.5
kg
EN 50178: 1997
Application domain
• Industrial.
With a di/dt of 100 A/µs.
Page 1/3
080711/9
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
w w w .lem.com
Current Transducer LF 2005-S
Isolation characteristics
Vd
Rms voltage for AC isolation test, 50 Hz, 1 min
6
kV
dCp
dCl
CTI
Creepage distance
Clearance distance
Comparative Tracking Index (Group I)
Min
29.1
27.1
600
mm
mm
Application examples
According to EN 50178 and IEC 61010-1 standards and following conditions :
• Over voltage category OV 3
• Pollution degree PD2
• Non-uniform field
EN 50178
IEC 61010-1
Rated isolation voltage
Nominal voltage
Single isolation
4000
4000
Reinforced isolation
2000
2000
dCp, dCI
Safety
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the manufacturer's
operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/3
080711/9
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
w w w .lem.com
Dimensions LF 2005-S
(in mm. 1 mm = 0.0394 inch)
Left view
Front view
Connection
Top view
Mechanical characteristics
Remarks
• General tolerance
• Fastening transducer
• IS is positive when IP flows in the direction of the arrow.
• Temperature of the primary conductor should not exceed
Flat or vertical position
Recommended fastening torque
• Primary through-hole
Or
• Connection of secondary
± 0.5 mm
4 holes ∅ 6.5 mm
4 M6 screw steel
5.5 Nm or 4.05 Lb. - Ft.
60.5 x 20.5 mm
∅ max 57 mm
S3P-VH
100°C.
• Dynamic performances (di/dt and response time) are best
with a single bar completely filling the primary hole.
• This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
Page 3/3
080711/9
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
w w w .lem.com